EVER POWERLINE DARK 33 10 - 40 kVA UPS Operating Manual
41
Technical Assistance, phone: +48 61 6500 400
2019-06-10 14:36 Type 01
Alarms
J9 terminal can signal the presence of an alarm. The presence of at least one alarm
closes or opens the relay’s contacts (depending on the configuration of the
connector). Fig. 34 presents the manner of making the connection. Table 9 presents
the pinout and the relevant description.
Fig. 34: Connections for J9 terminal
Table 9. J9 terminal pinout
Pin no.
Name
Description
J9-1
ALARM_NC
A relay informing about the presence of an alarm - normally
closed (J9-1 and J9-3). Opening of the relay indicates that an
alarm is present.
J9-2
ALARM_NO
A relay informing about the presence of an alarm - normally open
(J9-2 and J9-3). Closing of the relay indicates that an alarm is
present.
J9-3
GND
Common for NO and NC
No mains
J10 terminal is capable of signalling that there is no mains. Fig. 35 presents the
manner of making the connection. Table 10 presents the pinout and the relevant
description.
Fig. 35: Connections for J10 terminal