15. Shut down the external REPO breaker. Check the change of the functional state
on the display of the UPS unit.
16. Shut down the external REPO breaker and restart the UPS unit.
PARALLEL OPERATION
To improve the reliability of the system, the POWERLINE RT UPS units can operate
as a parallel system with redundancy of 1+1. In such system, the additional UPS unit
is connected in parallel and takes over a part of the system’s load. If one unit fails,
the other one takes over the load. It is possible to connect max. 2 units (1+1).
Installation and handling
1. Before installing a new UPS unit, prepare input and output cables, input and
output lines protections, as well as the 15-pin cable used for connecting 2 parallel
units (not included). The length of the communication cable (parallel) should not
exceed 3 m. Wires should be placed according to installation instructions, same
as for a single unit, with additional safeguards.
2. Every unit must be equipped with an independent battery set.
3. Connections should be made according to diagrams shown in figures 23 and 24;
make sure all fuses are disconnected.