EVER UPS POWERLINE RT 6000 / 10000 series instruction manual
57
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2017-01-05 13:16
TECHNICAL PARAMETERS
PARAMETERS \ TYPE
POWERLINE RT
POWERLINE RT 6000
POWERLINE RT 10,000
Index
T/PWRLRT116K00/00
T/PWRLRT-1110K0/00
Output power (apparent / active)
1)
6 kVA / 5,4 kW
10 kVA / 9 kW
GENERAL AND ENVIRONMENTAL DATA
Topology
VFI (on-line, VFI-SS-111)
Number of voltage phases (input / output)
1 / 1
Housing type
2)
Rack / Tower
Max. efficiency (for VFI)
˃ 92 %
˃ 93 %
Efficiency (for ECO)
˃ 96 %
˃ 97 %
Operating temperature
3)
0 ÷ +40 °C
Storage temperature
0 ÷ +40 °C
Relative humidity during operation
< 95% (no condensation)
Relative humidity during storage
< 95% (no condensation)
Elevation
4)
up to 1000 m
Protection class
IP20
Working environment
Office / industrial rooms with low level of pollution
Cooling
Forced, with internal fans
Cooling air temperature
< 25°C
Radiated heat for nominal operating conditions
< 1600 BTU / h
< 2300 BTU / h
INPUT
Rated voltage (effective value)
230 V AC
Input voltage range (effective values)
and tolerance
120 ÷ 276 V AC ± 3%
Rated current
29 A
47 A
Rated frequency, input voltage
50 / 60 Hz
Frequency range and tolerance
45 ÷ 55 / 54 ÷ 66 ±1 Hz
PF power factor
≥0.99
Total harmonic distortion, input current (THDi)
< 5%
OUTPUT
Rated voltage (effective value)
230 V AC
Input voltage range (effective values)
and tolerance - mains-based operation
208 V AC / 220 V AC /
230 V AC
/ 240 V AC ± 1 %
(The output voltage is adjusted from the LCD panel. The default value is 230 V AC.)
Input voltage range (effective values)
and tolerance - battery operation
208
V AC / 220 V AC /
230 V AC
/ 240 V AC ± 1 %
(The output voltage is adjusted from the LCD panel. The default value is 230 V AC.)
Rated current
26.1 A
43.5 A
Output voltage waveform (battery / mains-based
operation)
Sine / Sine
Frequency range (tolerance) - mains-based
operation
50 / 60 ± 0,5 Hz
(Same as the input or selected for the frequency conversion mode. In such a case a 20%
power reduction occurs.)
Frequency range (tolerance) - battery operation
50 / 60 ± 0,5 Hz
(Same as the input or selected for the frequency conversion mode. In such a case a 20%
power reduction occurs.)
Static voltage regulation
± 1%
Total harmonic distortion, output current (THDu)
< 2% for Pmax (linear)
< 5% (non-linear according to PN-EN 62040-3)
CF peak ratio
3:1
Switching time to battery mode
0 ms
Switching time to return to the mains-based
operation
0 ms
Overload capacity
5)
102 % ÷ 130 % - 2min
130 % ÷ 150 % - 30 s
> 150 % - 100 ms