EVER UPS POWERLINE RT 6000 / 10000 series instruction manual
2017-01-05 13:16
Technical Support, tel.: +48 61 6500 400
www.ever.eu
58
PARAMETERS \ TYPE
POWERLINE RT
POWERLINE RT 6000
POWERLINE RT 10,000
BATTERIES AND BACKUP TIMES
Internal batteries
12 V / 5 Ah VRLA
12 V / 9 Ah VRLA
Total number of internal batteries
1 x 15
1 x 20
Maximum permissible combined capacity of
internal battery pack
5 Ah
9 Ah
External battery packs
Yes
Maximum number of battery packs
4
Backup time using internal battery pack (100% /
80% / 50% of Pmax)
3 / 5 /8 min.
4 / 6 / 11 min.
Backup time using internal bat battery
pack (100% / 80% / 50% of Pmax)
10 / 14 / 26 min.
11 / 15 / 27 min.
Rated voltage for the DC circuit
180 V DC
240 V DC
Maximum charging time for UPS internal
batteries - after batteries have been 80%
discharged
≤ 4 h
Charging current, maximum
1 A
1.7 A
MECHANICAL PARAMETERS
Dimensions (height. x width x depth)
132 (3U) x 438 x 698 mm
215,5 (5U) x 438 x 704 mm
Weight
6)
46.2 kg
79.2 kg
Weight for transporting (gross)
6)
50.7 kg
86.6 kg
Dimensions for transporting (height. x width x
depth)
280 x 585 x 950 mm
355 x 585 x 965 mm
Position in transit
Horizontal
PROTECTIONS AND SAFEGUARDS
Input protection
Against overvoltage (Anti-surge)
Output protection
Inverter-based operation – electronic overload protection
Short circuit protection - output socket
protection
2 x Automatic fuse 15 A / 250 V AC
Short circuit protection - output socket
protection
4 x Automatic fuse 20 A / 250 V AC
FEATURES AND ADDITIONAL FUNCTIONS
UPS power supply connection
Terminal strip
Output connections (socket type and quantity)
4x IEC 320 C13 (10 A)
2x IEC 320 C19 (16 A)
Terminal strip
8x IEC 320 C19 (16 A)
Terminal strip
EPO
Yes (NC)
Manual BYPASS switch
Yes
Signaling
Acoustic and visual; LCD display
Communication interface
RS 232, USB, parallel operation communication port,
SNMP / HTTP network management card - optional
AS 400 card with volt-free contacts - optional
Monitoring and management software
PowerSoft Professional
STANDARDS APPLIED
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Caution: The manufacturer reserves the right to change the above listed parameters without notice.
ADDITIONAL NOTES:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load
current.
2)
The Rack Kit is optional.
3)
With internal batteries 5 ÷ 35°C. Constant exposure of the device to environment temperature over +25°C results in reducing
battery life.
4)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.
5)
With prolonged operation with recommended load.
6)
Weight of the UPS unit quoted for typical battery set.