62
Inverter voltage too
high
Alarm code: 32
Overvoltage occurred in the inverter of the UPS
unit.
If the UPS unit is powering a device, it will switch to
the bypass mode. Contact service support.
Inverter voltage too
low
Alarm code: 33
A voltage drop occurred in the inverter of the UPS
unit.
If the UPS unit is powering a device, it will switch to
the bypass mode. Contact service support.
Failure of the soft
start of the inverter
Alarm code: 34
Inverter’s soft start has failed
Contact service support.
Charger failure
Alarm code: 15
The UPS unit confirms failure of the charging unit.
The UPS unit switches OFF the charging circuit until
the next power cycle. Contact service support.
Battery voltage too
high
Alarm code: 16
Battery voltage is too high.
The UPS unit will switch off the charging circuit until
the battery voltage becomes proper. Contact service
support.
Critical failure of the
EEPROM memory
Alarm code: A3
The UPS unit could not successfully read the
EEPROM memory.
Contact service support.
Reverse power during
parallel operation
Alarm code: E1
Input line voltage occurring at the output of one
UPS unit or the difference between voltages of
lines exceeds 1 V.
Ensure proper connection of input lines of the UPS
units.
Communication loss
between UPS units in
a parallel connection
Alarm code: E2
The communication cable between two units has
been disconnected or damaged.
Check the connection. If damaged, replace the cable.
Then, switch on both units, so they can switch from
the bypass mode to the normal mode.
Batteries missing in
one of the units.
Alarm code: E6
The batteries circuit has been disconnected in
one of the units.
Check if all batteries are properly connected. If the
situation persists, contact service support.
No power in the input
circuit of one of the
units.
Alarm code: E7
Open input circuit in one of the units.
Check input cables connections of the UPS units and
the condition of input protections.
No power in the
bypass circuit of one
of the units.
Alarm code: E8
Open bypass circuit in one of the units.
Check bypass lines cable connections of the UPS
units and the condition of input protections.
Different operation
modes
Alarm code: E9
UPS units have been set to different operation
modes (ECO, inverter, normal).
Same operation mode should be set for all units. UPS
units working in parallel must work in the same
operation mode.
Different UPS units
powers
Alarm code: EA
UPS units with different rated powers have been
connected for parallel operation.
Only UPS units with the same rated power can be
connected for parallel operation.
ECO mode in parallel
operation
Alarm code: EB
ECO mode has been set in the parallel system.
UPS units cannot work in the ECO mode as a parallel
system. Turn the mode off.