EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
20
the UPS operates in frequency converter mode.
The function may be activated via the LCD display (settings menu
005). The UPS may be loaded up to 60% of its rated power in the
inverter mode.
EMERGENCY Mode.
The UPS unit may switch to EMERGENCY mode either as a result of
an overload, a shorted output, internal fault(s), exceeding the
permissible temperature range of the inverter or internal batteries or
triggered EPO. The UPS is switched off by the logic system and user's
intervention is required. The LCD displays the message code (e.g.
E03) or the type of error (e.g. A64).
MENU STRUCTURE - CONFIGURATION OF UPS UNIT
The LCD panel can also be used to configure the unit's selected parameter and to
active / deactivate its operation modes. To enter the settings menu press and keep
depressed the ENTER button for over 5 s. The settings menu is only available when
the UPS operates in the BYPASS or STANDBY mode. Table 5 shows POWERLINE
RT PLUS unit's menu structure with the possible settings.
Table 5. UPS configuration
Parameter ID
Parameter
Available settings
Default
settings
LCD display
001
Output voltage
208 V AC / 220 V AC /
230 V AC / 240 V AC
230 V AC
002
Output
voltage
frequency
50 Hz / 60 Hz
50 Hz
003
ECO
mode
with
voltage tolerance at
which the mode is
deactivated.
0% (Disabled)
10% / 15% (Enabled)
0%
004
BYPASS mode
[dis]
– Disabled
[EnA]
– Enabled
Enabled