EVER POWERLINE RT PLUS UPS Operating Manual
21
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
005
INVERTER mode
[dis]
– Disabled
[EnA]
– Enabled
Disabled
006
Selecting the EPO
function (remote
emergency power off)
or ROO function
(remote ON/OFF)
EPO / ROO*
EPO
007
Number of battery
modules
0bP / 1bP / 2bP / 3bP
/ 4bP / 5bP / 6bP /
7bP / 8bP / 9bP / AbP
0
008
Activating the BYPASS
mode when the UPS is
not logically on
[dis]
– Disabled
[EnA]
– Enabled
Disabled
009
Sound signaling
[dis]
– Disabled
[EnA]
– Enabled
Enabled
010
Controlled output
sockets
[dis]
– Disabled
[EnA]
– Enabled
Enabled
PROTECTION
Overload protection
In the mains mode, the overload in the range of 105-110% is indicated by an
intermittent sound signal and message E14 on the display. If the overload condition
stays at the 110-120% level and when the function "switch to BYPASS if overloaded"
is enabled (the function can be enabled through external software), the UPS unit
switches to the bypass mode after 60 s and signals the overload (message A64).
When the overload condition ceases, the unit reverts to the mains mode. If the
function "switch to BYPASS if overloaded" is disabled, output sockets are
disconnected after 60 s. The LCD displays message E14.