EVER POWERLINE RT PLUS UPS Operating Manual
23
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
enters the EMERGENCY mode (error code A66). The output voltage will be restored
only after the user’s intervention to reset the trigger to the disabled position (trigger's
default state) and to switch the UPS logically on again.
The EPO connection contacts show safe voltage levels isolated from the remaining
UPS unit systems.
CAUTION!
The EPO circuit must be a separate circuit and it is forbidden
to connect it with other installations.
The Remote ON/OFF (ROO) function allows the user to remotely switch the UPS on
and off. The UPS is switched off by opening the unit's contacts. Closing the contacts
restarts the UPS. Selecting the ROO function deactivates the possibility of logical
switching on / off the power supply using the control panel.
INSTALLATION
INSTALLING THE UPS UNIT
After unpacking, please inspect the device for damages. The UPS should only be
used in rooms where the dust, temperature, and humidity levels are within the
device's specifications.
Appropriate cooling conditions must be ensured for the UPS to work properly. For
this reason, the distance between the UPS and other objects should not be less than
20 cm.
The mains socket the UPS is to be connected to, should be located near the unit
(maximum distance
– 1.8 m) and should be easily accessible.
CAUTION!
No extension cords should be used for connecting the UPS
unit.
CAUTION!
Installing a UPS unit in proximity of flammable materials or
substances is strictly prohibited!
Due to the type and placement of the fuses in the UPS, it is recommended that the
protection systems in the building's electric system be used as one of protection
levels.
This is necessary to ensure short circuit protection for the UPS. The