EVER POWERLINE RT PLUS UPS Operating Manual
43
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
The following functionalities are implemented in the network card:
SNMP agent
– provides the management of the power supply system using the
PowerSoft management software or another type of management / control
software package installed by the user.
HTTP server
– allows monitoring and possible modification of the UPS
parameters using a www browser.
OPERATING INSTRUCTIONS
CAUTION!
The UPS is a class C2 device. In domestic environment, the
UPS may interfere with reception of radio waves so the user may be
forced to implement additional preventive measures.
CAUTION!
There are no user-serviceable parts inside the UPS unit.
Damaging the warranty seal will render any product warranty void.
Any repairs should be carried out only by suitably qualified service technicians
holding professional licenses required by law.
The UPS power supply unit may operate below the expected performance
parameters if the connected equipment requires high pulsed power. In practice,
this means that even if the average power of the connected equipment is within
the permitted UPS unit’s range, the load could still shut the UPS down. The
reason for this is that such a high level of power drawn instantaneously by the
connected equipment considerably exceeds the UPS unit’s power rating. As a
result, system overload is detected, leading to the UPS unit’s shutdown.
It is recommended that battery inspection and maintenance is carried out only by
suitably qualified service technicians who are familiar with the battery system and
who take necessary precautions.
When replacing the battery, always use the same type and the same number of
batteries. Using batteries of incorrect type may result in explosion.
WARNING!
Ensure suitable battery fire protection due to potential risk of
explosion.