EVER POWERLINE RT PLUS UPS Operating Manual
2019-11-25 11:43
Technical Support, phone: +48 61 6500 400
44
WARNING!
Never attempt to open the battery. Always ensure suitable
battery protection against potential damage. Spilled electrolyte is harmful
to the eyes and skin, and could be toxic.
INTERACTION WITH ELECTRICAL GENERATORS
The POWERLINE RT PLUS UPS units are ONLINE (VFI) class units designed to
synchronize voltage with the mains voltage. The unit has been designed to tolerate
voltage fluctuations in a certain range and changes of the frequency in relation to the
rated frequency of 50 Hz. Power generators are characterized by variable frequency
of the output voltage, which depends on the changes in the load values. If variations
of frequency of the output voltage exceed the allowed tolerance thresholds, the UPS
will consider the parameters of the input voltage to be incorrect and switch to the
battery mode.
STORAGE, MAINTENANCE AND TRANSPORT
The power supply unit should be stored in a cool and dry place, in its working
position, with the battery fully charged:
at a temperature between 0°C ÷ + 30°C, the battery should be charged every 6
months;
at a temperature b 30°C ÷ + 40°C, the battery should be charged every
3 months.
In order to maintain the battery in good shape, disconnect the device from the
mains every 6 months in order to deplete the battery (with connected load) and
then charge them again.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the battery has not been recharged. In such
cases please contact your service agent.
To ensure maximum battery life, ambient temperature around the operating UPS
units should be 15-
25 ºC.