EVER POWERLINE RT PLUS UPS Operating Manual
47
Technical Support, phone: +48 61 6500 400
2019-11-25 11:43
TECHNICAL PARAMETERS
PARAMETERS \ TYPE
POWERLINE RT PLUS
POWERLINE RT PLUS
1000
POWERLINE RT PLUS
2000
POWERLINE RT PLUS
3000
Index
T/PWPLRT-111000/00
T/PWPLRT-112000/00
T/PWPLRT-113000/00
Output power (apparent / active)
1)
1000 VA / 1000 W
2000 VA / 2000 W
3000 VA / 3000 W
GENERAL AND ENVIRONMENTAL DATA
Topology
VFI (on-line, VFI-SS-111)
Number of voltage phases (input / output)
1 / 1
Housing type
2)
Rack / Tower
Max. efficiency (for VFI)
87 %
89 %
90 %
Efficiency (for ECO)
95 %
Operating temperature
3)
0 ÷ +40 °C
Storage temperature
0 ÷ +40 °C
Relative humidity during operation
< 95% (no condensation)
Relative humidity during storage
< 95% (no condensation)
Altitude above sea level
4)
up to 1000 m
Protection class
IP20
Working environment
Office / industrial rooms with low level of pollution
Cooling
Forced, with internal fans
Cooling air temperature
< 25°C
Radiated heat for nominal operating
conditions
< 510 BTU / h
< 850 BTU / h
< 1200 BTU / h
INPUT
Rated voltage (effective value)
230 V AC
Input voltage range
(effective values) and tolerance
5)
110 ÷ 300 V AC ± 5%
Rated current
5 A
9.8 A
14.5 A
Rated frequency, input voltage
50 / 60 Hz
Frequency range and tolerance
40 -
70 Hz ± 5 %
PF power factor
≥0.99
Total harmonic distortion, input current (THDi)
< 10 %
OUTPUT
Rated voltage (effective value)
230 V AC
Output voltage range (effective value) and
tolerance - mains operation
6)
208 V AC / 220 V AC /
230 V AC
/ 240 V AC ± 1 %
(The output voltage is adjusted from the LCD panel. The default value is 230 V AC.)
Output voltage range (effective value) and
tolerance - backup operation
6)
208
V AC / 220 V AC /
230 V AC
/ 240 V AC ± 1 %
(The output voltage is adjusted from the LCD panel. The default value is 230 V AC.)
Rated current
4.4 A
8.7 A
13.1 A
Output voltage waveform
(backup / mains operation)
Sine / Sine
Output voltage rated frequency
50 / 60 Hz
Frequency range (tolerance)
- mains operation
50 / 60 Hz ± 0.5 %
(Same as the input or selected for the frequency conversion mode. In such a case, a
40% power reduction occurs.)
Frequency range (tolerance)
- backup operation
50 / 60 Hz ± 0.5 %
(Same as the input or selected for the frequency conversion mode. In such a case, a
40% power reduction occurs.)
Static voltage regulation
± 1%
Total harmonic distortion, output current
(THDu)
< 3% for Pmax (linear)
< 5% (non-linear according to PN-EN 62040-3)
CF peak ratio
3:1
Switching time to battery mode
0 ms
Switching time to return to the mains-based
operation
0 ms
Overload capacity
7)
105% ÷ 110% - warning
110% ÷ 120% - 60 s (switching to the bypass mode)
> 120% - 100 ms (UPS switches off)