Instruction manual for POWERLINE 33 series UPS
2010/06/22
www.ever.eu
8
PAGES
SCREENSAVER
Description: Information page that appears as a screensaver after 5 minutes of the
last button being pressed. It turns off LCD illumination, as well.
Type:
read
Parameters:
Q
- battery charge level
U+
- hot battery cell (+) voltage
U-
- cold battery cell (-) voltage
Owy
- battery load level
Tau
- expected backup duration
TrybPracy - operation mode
i: …, A: … - additional information according to the table
General messages (i:) describe all the operation modes, except for
EMERGENCY, which is signalled with emergency messages
General messages
Alerts
Abbreviation
Power supply
Message
Description
i:Ladowanie
Charging
A:Zwarcie
Short circuit
F)
i:Przeci
ąŜ
enie
Overload
A:Przeci
ąŜ
enie
Overload
F)
i:PrzegrzanieProst
Rectifier block overheating
A:PrzegrzanieProst
Rectifier block overheating
P)
i:PrzegrzanieFal
Inverter block overheating
A:PrzegrzanieFal
Inverter block overheating
F)
i:OczekNaLadunekMin
Waiting after STANDBY
A:UszkAkumulatora
Damaged batteries
P)
i:AkumulatorRozlad
90 s backup time left
A:EPO
Emergency EPO
F)
i:Serwis
Periodic servicing
recommended
A:BladWewProstownika
Internal rectifier block error
P)
i:Bypass
BYPASS active
A:BladWewFalownika
Internal inverter block error
F)
i:BrakKomProst
No communication with
rectifier block
F) message started by KasujAwarieFal
(Configuration 3/4)
i:BrakKomFal
No communication with
inverter block
P) message ended by KasujAwarieProst
(Configuration 3/4)
i:ZlaKolejnoscFazByp
Incorrect phase order in
BYPASS
i:ZasBypPozaZakres
Exceeded BYPASS
parameters
i:OtwartyObwAku
Open battery circuit
i:ZasProstPozaZakres
Exceeded inverter block
parameters
Screen: