EVER POWERLINE RT PLUS 6000 / 10000 UPS Operating Manual
2020-03-20 13:06
Pomoc Techniczna, tel.: +48 61 6500 400
16
mode, buzzer will work again
Exit main
menu
Press this button for > 100ms & < 2s to exit the present menu to
default system status display menu or the higher level menu without
executing a command or changing a setting
Table 2. Visual signaling of specific states of the UPS unit
Status UPS
NORMAL LED
(green)
BATTERY LED
(orange)
BYPASS LED
(orange)
FAULT LED
(red)
Standby Mode
★
↑
Bypass Mode
●
↑
Turning on UPS
Δ
Δ
Δ
Δ
Online Mode
●
↑
Battery Mode
●
↑
ECO Mode
●
●
↑
Battery test
Δ
Δ
Δ
Δ
Fault
★
●
Warning
↑
↑
↑
★
●: Lightened constantly
Δ
: Lightened circularly (NORMAL-BATTERY-BYPASS-FAULT-NORMAL-
… )
★
: Flashing
↑
: Depended on the fault / warning status or other status (LED Lightened constantly or flashing)
Table 3. Sound signals for specific states of the UPS unit
Event
Acoustic signal
Fault active
Continous
Over Load
– Warning active 2 Beep every second
Other Warning active
Beep every second
Battery Mode
Beep every 4 seconds, if battery low, buzzer Beep every second
BYPASS Mode
Beep every 2 minutes
USER INTERFACE MENU STRUCTURE
The menu structure of POWERLINE RT PLUS units is show in Fig. 6. The structure
of the main menu consists of 6 branches (menus): menu
UPS status
, menu
Event
log
, menu
Measurements
, menu
Control
, menu
Identification,
menu
Settings
.
To navigate to the main menu in the tree from, press and hold the
button for
less than 1 s in the default functional state screen of the UPS unit.
Summary of Contents for POWERLINE RT PLUS 10000
Page 1: ......