PARAMETERS \ TYPE
SINLINE RT
1000
SINLINE RT
1200
SINLINE RT
1600
SINLINE RT
2000
SINLINE RT
3000
Part number
W/SRTLRT-
001K00/00
W/SRTLRT-
001K20/00
W/SRTLRT-
001K60/00
W/SRTLRT-
002K00/00
W/SRTLRT-
003K00/00
Output Power (Apparent / Active)
1)
1000 VA
650 W
1200 VA
850 W
1600 VA
1250 W
2000 VA
1650 W
3000 VA
2250 W
PROTECT
Input over current protection
Short-circuit protection
– Circuit breaker
10 A / 250 V AC
Short-circuit protection
–
Circuit breaker
16 A / 250 V AC
Surge Protection
Output over current protection
Electronic short-circuit and overload protection
DC over current (internal batteries)
Over current
ACCESSORY AND EXTRA FUNCTIONS
Power supply connection
1 x IEC 320 C14 (10 A)
1 x IEC 320 C20 (16 A)
Output connection (number and type of
sockets )
3 x IEC320 C13 (10 A)
2 x PL
6 x IEC 320 C13 (10 A)
2 x PL
Signalling
Acoustic and optical; LCD graphic display, LED
Communications interfaces
USB HID, SNMP/HTTP
Software
PowerSoft Professional
CERTIFICATION
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Note
: The manufacturer reserves the right to change the above listed parameters without notice.
* Charging time up to 90% battery capacity, following discharge with load equal to 80% Pmax (until the UPS switches off).
REMARKS:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load
current.
2)
The Rack Kit is available as an option.
3)
. Constant exposure of the device to environment temperature over +25°C results in reducing battery life.
4)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.