SINLINE XL series UPS – Instruction Manual
2010/01/27
www.ever.eu
27
CONFIGURING THE UPS'S PARAMETERS
PowerSoft Plus allows the user to change certain parameters of the UPS. To enable
this, the UPS must be connected to the computer with the cable provided by the
manufacturer. A list of these parameters together with available settings is presented
in the tables below.
Table 2
PARAMETER/FUNCTION
FACTORY
SETTING
CUSTOM SETTINGS
DESCRIPTION
Acoustic signalling
On
On/off
Only for the battery operation mode
Delay before standby mode
90 sec.
0 – 1000 sec.
Time between system shutdown and the
UPS switching to standby mode
Table 3
THRESHOLD (SWITCHING) VOLTAGE
UPS STATUS
Range
Default setting
BAT
→
MAINS + AVR
~155 ÷175 V
~165 V
MAINS + AVR
→
BAT
~150 ÷170 V
~160 V
MAINS + AVR
→
MAINS
~200 ÷210 V
~205 V
MAINS
→
MAINS + AVR
~195 ÷205 V
~200 V
MAINS
→
BAT
~250 ÷280 V
~265 V
BAT
→
MAINS
~245 ÷275 V
~260 V
BAT – battery operation mode
MAINS – mains operation mode
MAINS + AVR – mains operation mode with AVR system engaged
ADDITIONAL REMARKS
CAUTION: This is a C2-category UPS. In domestic environment the
product may interfere with reception of radio waves so the user may
be required to implement additional preventive measures.
WARNING! No service elements located inside the UPS are to be
modified by the end user.
•
Damaging the warranty seal shall void the warranty for the given device.
•
Any repairs should be conducted only by qualified technical support staff.
•
The UPS may not perform as expected if the powered equipment draws high
impulse power. In practice this means that even though mean power of the
protected equipment does not exceed the power range accepted by the UPS, the
equipment will cause the UPS to shut down. This happens because the powered
equipment temporarily draws power that significantly exceeds the nominal power