Instruction Manual for SUPERLINE series battery back-ups
2010/01/13
www.ever.eu
27
STARTING THE BATTERY BACK-UP
A correctly connected battery back-up may be started as follows:
1)
Verify whether the F3 and F4 circuit breakers are set to OFF; if not, set them to
OFF.
2)
Open the F1 and F2 fuse holders.
3)
Insert the correct fuse-element into the F1 fuse holder (do not close the holder).
4)
Insert the correct fuse-element into the F5 fuse holder and close it to close the
circuit.
5)
Insert the correct fuse element into the fuse holder on the battery module and
close the circuit by closing the holder.
6)
Close the F1 holder.
7)
Wait at least 10 seconds.
8)
Close the F2 holder – accumulators are now connected.
9)
Switch the F3 and F4 circuit breakers to ON.
10) Configure the battery back-up (when starting for the first time, if changes are
required).
11) Turn on the battery back-up via the user interface (KONTROLA 1/4; UPS).
Items 4 and 5 are to be performed only when additional battery modules are being
connected.
Afterwards the battery back-up begins normal operation in accordance with the
description below.
WARNING! Back-up's batteries reach their full capacity after
approximately a month of NORMAL operating mode.
POWERING OFF AND DISCONNECTING THE BATTERY BACK-UP
In order to disconnect the battery back-up completely, perform the below tasks in the
given order:
1)
Turn off the battery back–up via the user interface (KONTROLA 1/4; UPS) –
logical power off;
2)
Disable the safeguards of the basic and BYPASS lines in the room’s/building’s
switching station while the back-up is uninstalled.
3)
Set the F3 and F4 safeguards of the battery back-up to OFF.
4)
Disable safeguards F1, F2 and F5 by opening them and removing the fuse-
elements.
5)
If additional battery modules are connected to the back-up, repeat tasks from
item 4 for safeguards F1 and F2 on the modules.
6)
Remove the connector stoppers on the battery back-up and any modules.
7)
Disconnect the connecting cables from the switching station, battery back-up
and modules (also between individual modules). Never leave any cables
unconnected.
8)
Replace the protective stoppers.
9)
Close the F1, F2 and F5 fuse holders on the battery back-up and the F1 and F2
holders on the modules if the fuse-elements have been removed. Fuse-
elements should not be stored inside the battery back-up when it is not
installed.
Summary of Contents for Superline 10k
Page 1: ...1 ...