4. Command 0x06 (write single register)
Register
Variable
Description
0
L1PhaseOutputVoltage
L1 phase output voltage for the UPS in the inverter-based mode, quoted with the
resolution accuracy of 1V
1
L2PhaseOutputVoltage
L2 phase output voltage for the UPS in the inverter-based mode, quoted with the
resolution accuracy of 1V
2
L3PhaseOutputVoltage
L3 phase output voltage for the UPS in the inverter-based mode, quoted with the
resolution accuracy of 1V
3
UpperVoltageValue
Parameter/word used for configuration of the upper voltage value for the bypass system
to ensure correct supply parameters, quoted with the resolution accuracy of 1V
4
LowerVoltageValue
Parameter/word used for configuration of the lower voltage value for the bypass system
to ensure correct supply parameters, quoted with the resolution accuracy of 1V.
5
LowerVoltageFrequencyValue
Parameter/word used for configuration of the lower voltage frequency value for the
bypass system to ensure correct supply parameters, quoted with the resolution accuracy
of 1 Hz.
6
UpperVoltageFrequencyValue
Parameter/word used for configuration of the upper voltage frequency value for the
bypass system to ensure correct supply parameters, quoted with the resolution accuracy
of 1 Hz.
7
OverloadStop
Binary value, quoted in percentage of the maximum UPS output power, below which the
unit stops indicating output overload
and continues operation according to the configuration
8
DelayTimer
Binary parameter, quoted in seconds and used to switch off the inverter operation with a
given delay. This is to be configured to set the required delay value prior to setting the bit
“Command to switch the UPS to the waiting mode” by the software.
9
CapacityStandby
Binary value quoted as a percentage of the available capacity, used to delay the unit’s
exiting the STANDBY mode before reaching the required battery charge level.
10
CapacityBattery
Binary parameter, indicates the capacity of an individual battery.
11
NbrOfStringsBatteries
Binary parameter, indicates the number of battery sections currently connected to the
UPS unit (comprises the sum of internal and external batter sections).
12
ChargingCurrent
Binary parameter, indicates the value of the charging current, quoted with the resolution
accuracy of 0.1 A