Document No. 1112M001 Revision 1.8 Date: June 2013
26
250Vdc Grid Tie
Wire Size Table for Kestrel e400nb 3.5kW 250Vdc 14A
One Way
Distance
3% Power loss
4% Power loss
5% Power loss
20m (66ft)
1.0mm
²
(17)
1.0mm
²
(17)
1.0mm
²
(17)
40m (130ft)
2.5mm
²
(13)
1.8mm
²
(14)
1.5mm
²
(15)
60m (200ft)
3.5mm
²
(12)
2.7mm
²
(13)
2.1mm
²
(14)
80m (260ft)
4.7mm
²
(10)
3.5mm
²
(11)
2.8mm
²
(12)
100m (330ft)
5.9mm
²
(9)
4.4mm
²
(10)
3.5mm
²
(11)
120m (400ft)
7.0mm
²
(8)
5.3mm
²
(10)
4.2mm
²
(11)
48Vdc battery charging
Wire Size Table for Kestrel e400nb 3,5kW 48Vdc 65A
One Way
Distance
3% Power loss
4% Power loss
5% Power loss
20m (66ft)
30mm
²
(2)
23mm
²
(3)
18mm
²
(4)
40m (130ft)
60mm
²
(00)
46mm
²
(0)
36mm
²
(1)
60m (200ft)
92mm
²
(000)
70mm
²
(00)
55mm
²
(0)
110Vdc battery charging
Wire Size Table for Kestrel e400nb 3,5kW 110Vdc 37A
One Way
Distance
3% Power loss
4% Power loss
5% Power loss
20m (66ft)
6mm
²
(9)
4,5mm
²
(10)
4mm
²
(11)
40m (130ft)
16mm
²
(5)
12mm
²
(6)
10mm
²
(7)
60m (200ft)
25mm
²
(3)
16mm
²
(5)
12mm
²
(6)
80m (260ft)
35mm
²
(1)
25mm
²
(3)
16mm
²
(5)
100m (330ft)
50mm
²
(0)
35mm
²
(1)
25mm
²
(4)