1.2 Turbine Operating Procedures
A standard start and stop procedure is included in this product manual
(Annexure 4). It is recommended that a label showing this procedure be
visible adjacent to the wind turbine tower.
A “T” bar is supplied to operate the tower brake. This “T” bar should be
stored in a safe but accessible location and never left in position on the
tower.
Standard Operating Procedure
This procedure gives a clear action sequence for the following procedures:
i) Procedure for starting and activation
ii) Procedures during normal running
iii) Procedure for stopping and de-activation
iv) Procedure for routine maintenance
Procedure for Starting
(Assumption: The turbine is braked and electrically isolated)
•
Ensure that all personnel and animals are well clear of the
turbine tower
•
Engage the turbine fuse holder F1/F2 in the interface unit to
connect the turbine.
•
Release the electrical brake switch S1 located in the interface
unit
•
Approach the tower base and insert the “T” bar into the brake
winch.
•
Apply light pressure to the brake and release the ratchet
lever.
•
Release the mechanical brake by unwinding the brake winch.
•
Observe the turbine to start rotation in the wind.
•
Re-apply the ratchet lever and remove the “T” bar.