VII - GAS PRESSURE SETTING PROCEDURE
All settings/adjustments must be performed
by a qualified Service Technician.
1.
Turn unit off at power source and turn off the gas to the water heater.
2.
Remove the front cover from the water heater.
3.
Remove the gas pressure test port plug. Connect manometer to this port. (See Figure #1 for
location of the test port plug.) Turn on the gas and power to the water heater.
4.
Flow water through the water heater at the maximum flow rate obtainable, at least three
gallons per minute.
5.
To adjust the "
Low
" fire pressure, use small (pocket) common screwdriver to set combustion
control dip switch #7 to the "
ON
" position, and switch #8 to the "
OFF
" position (see figure #2
for location of combustion control switches.) This will put the unit into forced low fire. Check
the pressure reading on your manometer. If the pressure needs adjusting, remove the rubber
plug from the bottom of the water heater casing (located beneath the regulator), to access the
regulator adjustment screw. Adjust the regulator screw to achieve the correct gas pressure.
(See figure #1 for location of the regulator adjustment screw.) Below are the proper pressures
for "
Low
" fire, per gas type.
Propane
0.88" w.c. @ 10" w.c. supply
(Low fire rate of 15,000 BTU's)
Natural
0.56" w.c. @ 6" w.c. supply
(Low fire rate of 15,000 BTU's)
6.
To adjust the "
High
" fire pressure, use small (pocket) common screwdriver to set combustion
control dip switch #7 to the "
ON
" position, and switch #8 to the "
ON
" position (see figure #2
for location of the combustion control switches), this will put the unit into forced high fire.
Check the pressure reading on your manometer. If the pressure needs adjusting, use small
(pocket) common screwdriver to adjust the high pressure "
Pot
". (See figure #2 for location of
"
high pressure setting pot
"). Below are the proper pressures for "
High
" fire.
Propane
5.1" w.c. @ 10" w.c. supply
(High fire rate of 199,000 BTU's)
Natural
3.4" w.c. @ 6" w.c. supply
(High fire rate of 199,000 BTU's)
7.
Verify both low and high fire pressures by placing the water heater into "
Forced Low Fire
" and
"
Forced High Fire
" as described in steps 5 and 6 above. This completes the gas pressure
setting procedure. Dip switches #7 and #8 (combustion control switches),
MUST
be returned
to the "
Off
" position, after setting the pressures.
Refer to page 12 for factory default dip switch settings.
44
Summary of Contents for IGE-199C-5N
Page 7: ...I GENERAL INFORMATION cont CUT AWAY ILLUSTRATION 7...
Page 8: ...I GENERAL INFORMATION cont SCHEMATIC ILLUSTRATION 8...
Page 19: ...V SEQUENCE OF OPERATION cont OPERATION SEQUENCE FLOW CHART 19...
Page 20: ...20 V SEQUENCE OF OPERATION cont OPERATION SEQUENCE FLOW CHART...
Page 21: ...V SEQUENCE OF OPERATION cont SEQUENCE TIMING CHART 21...
Page 22: ...22 V SEQUENCE OF OPERATION cont SEQUENCE TIMING CHART...
Page 28: ...VI TROUBLE SHOOTING cont WIRING SCHEMATIC 28...
Page 53: ...X PARTS BREAKDOWN DISASSEMBLED VIEW CABINET 53...
Page 54: ...X PARTS BREAKDOWN DISASSEMBLED VIEW INTERNALS 54...
Page 55: ...X PARTS BREAKDOWN DISASSEMBLED VIEW INTERNALS 55...
Page 56: ...X PARTS BREAKDOWN DISASSEMBLED VIEW ELECTRICAL 56...
Page 59: ...59 Notes...