INFORMATION FOR NEBS COMPLIANT VERSIONS
The intra-building port(s) of this equipment is suitable for connection to
intra-building or unexposed wiring or cabling only. The intra-building
port(s) of the equipment MUST NOT be metallically connected to interfaces
that connect to the OSP or its wiring. These interfaces are designed for use
as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-
1089-CORE, Issue 4) and require isolation from the exposed OSP cabling.
The addition of Primary Protectors is not sufficient protection in order to
connect these interfaces metallically to OSP wiring.
The intra-building port(s) of the equipment or subassembly must use
shielded intra-building cabling/wiring that is grounded at both ends.
This equipment is to be connected to a Common Bonding Network. See
Installation section for further information.
This equipment is to be installed in the network telecommunication
facilities.
To ensure that radiated emissions do not exceed NEBS requirements, all
Ethernet (Cat-5 or better) connections must use shielded cable.
The use of unshielded Ethernet cable may cause excessive electromagnetic
radiation in excess of NEBS specifications.