3) The indoor main PCB damage.
Solution:
Replace the indoor main PCB.
1
.5.3 Display E3, E7
Reasons:
1) Outdoor pipe temp sensor, outdoor temp sensor & exhaust temp sensor
connection terminal loose or not
plugged in.
Solution:
Check the connecter of sensor and slot, if loose or not plugged in, please connect again.
2) Outdoor pipe temp sensor, outdoor temp sensor & exhaust temp sensor damage (short or broken).
Solution:
Check and replace the sensor.
3) Outdoor PCB damage.
Solution:
Check and replace the outdoor PCB.
1
.5.4 Display E8
Reasons:
1) Outdoor discharge pipe temp sensor
connection terminal loose or not plugged in.