background image

E2630-LEL

Rev 23.03.2021

Butane

A colorless flammable gas that is heavier than air. The term “butane” is used for any of two
structural isomers (n-butane or iso-butane, with unbranched and branched-chain
respectively) or for their mixture. Occurs in light petroleum fractions.

Butane is used mainly as a fuel and as a feedstock in organic synthesis. It is applied also
as a propellant in aerosol sprays and may be used as an ozone-friendly refrigerant.

Mixtures of butane with propane and other hydrocarbons are referred to as LPG (liquefied
petroleum gas).

Chemical formula

n-butane

CH

3

CH

2

CH

2

CH

3

iso-butane

CH

3

CH(CH

3

)CH

3

Molar weight

58

Relative gas density (to air)

2.0

Conversion

1 ppm = 2.38 mg/m

3

Boiling point

-0.56 °C

−11.7 °C

Low explosive limit (LEL), % vol. in air

1.4* (1.6**)

1.5* (1.8**)

Upper explosive limit (UEL), % vol. in air

8.4

9.6

Odor

Gasoline-like odor

Hazards

Highly flammable.

Inhalation of butane can cause euphoria, drowsiness,

narcosis, asphyxia, cardiac arrhythmia, fluctuations in

blood pressure, and temporary memory loss, when

abused directly from a highly pressurized container, and

can result in death from asphyxiation and ventricular

fibrillation.

Exposure

limits

(NIOSH)

TWA

1900 mg/m

3

/800 ppm

Not established

4

Summary of Contents for E2630-LEL

Page 1: ...Combustible Gas Detector E2630 LEL User Manual...

Page 2: ...ications 8 Product description 9 Safety requirements 9 Operating conditions 9 Installation guidelines 9 Mounting dimensions 11 Connections 12 Operation 13 Sensor probe handling 14 Maintenance 15 Calib...

Page 3: ...Ethyne Chemical formula HC CH Molar weight 26 Relative gas density to air 0 90 Conversion 1 ppm 1 06 mg m3 Boiling point 84 C Low explosive limit LEL vol in air 2 3 2 5 Upper explosive limit UEL vol...

Page 4: ...are referred to as LPG liquefied petroleum gas Chemical formula n butane CH3CH2CH2CH3 iso butane CH3CH CH3 CH3 Molar weight 58 Relative gas density to air 2 0 Conversion 1 ppm 2 38 mg m3 Boiling poin...

Page 5: ...e electrolysis of aqueous solutions In industrial production the main source of hydrogen is hydrocarbons Chemical formula H2 Molar weight 2 Relative gas density to air 0 07 Conversion 1 ppm 0 0818 mg...

Page 6: ...Synonyms Marsh Gas Natural Gas Carbon tetrahydride Hydrogen carbide Chemical formula CH4 Molar weight 16 Relative gas density to air 0 55 Conversion 1 ppm 0 65 mg m3 Boiling point 161 49 C Low explosi...

Page 7: ...r weight 44 Relative gas density to air 1 55 Conversion 1 ppm 1 80 mg m3 Boiling point 42 C Low explosive limit LEL vol in air 1 7 2 1 Upper explosive limit UEL vol in air 9 5 Odor Odorless when pure...

Page 8: ...ace UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm signaling Buzzer 2 kHz 85 dB red LED LEDs Green red operation fault red gas alarm Enclosure Grey ABS wall mount protection class IP65 Dimensi...

Page 9: ...ctricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if the wrong power supply is connected External circuits connected to the equi...

Page 10: ...d be accessible for maintenance and repair The aforementioned conditions above will affect the coverage area of the device however the coverage area for a detector is usually between 2 5 to 5 meters r...

Page 11: ...E2630 LEL Rev 23 03 2021 Mounting dimensions 11...

Page 12: ...mm2 We recommend to strip the wire end by 5 6 mm and use the wire end sleeves To connect the wire loosen the screw insert the wire end into the terminal hole and tighten the screw The outer diameter...

Page 13: ...gas concentration exceeds the LOW alarm setpoint the bottom red LED starts flashing at a rate of 1 Hz and the relay RE1 switches over The first alarm stops automatically if the gas concentration drop...

Page 14: ...lter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sensor Do not remove the filter as i...

Page 15: ...acturer with standard gas mixtures before delivery Provided that the sensor is used under moderate conditions field recalibration is recommended every 12 months Please contact your dealer for more inf...

Page 16: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...