34000 Autry Street, Livonia, MI 48150 | 800.968.5530 | Fax 734.419.0209 | www.hamiltonengineering.com | LIT91127US REV 5/2018
Page 15
(TABLE 3-2) PROPANE SUPPLY PIPING
(Based on 11" WC supply pressure)
C. GAS TABLES
D. GAS VALVE SETUP
Models 119–399
Model 599
2
1
3
2
1
3
4
(DO NOT TOUCH LEFT
DO NOT ADJUST
increase
increase
HAND GAS VALVE!)
(FIGURE 3-2) EVO MODELS 79–399
(FIGURE 3-3) EVO MODEL 599
(TABLE 3-1) NATURAL GAS SUPPLY PIPING
Nominal
Internal
Length
of
Pipe
(Feet)
Iron Pipe Diameter
Size
(in.)
(inches)
10
20
30
40
50
60
70
80
90
100
125
150
200
BTUs
per
HR
x
1,000
3/4
0.824
363
249
200
171
152
138
127
118
111
104
93
84
72 }
1
1.049
684 470
377
323
286
259
239
222
208
197
174
158
135 }
1-1/4
1.380
1,404 965
775
663
588
532
490
456
428
404
358
324
278 }
1-1/2
1.610
2,103 1,445 1,161
993
880
798
734
683
641
605
536
486
419 }
2
2.067
4,050 2,784 2,235 1,913 1,696 1,536 1,413 1,315 1,234 1,165 1,033
936
801 }
(Based on 0.60 specific gravity for natural gas at 0.5" WC pressure drop; DOE standard is 1100 BTU per
cubic foot of natural gas.)
1 Run the gas supply line in accordance with all applicable codes.
2. Locate and install manual shut off valves in accordance with state and local requirements.
GAS CONNECTION