6-Electrical connection
11
Before starting any electrical connection,
check that the electrical supply
corresponds to the specification
indicated on the unit's maker's plate and
to the unit's electrical characteristics
table.
Important: It is the responsibility of the
installer to provide circuit breaker
protection, corresponding to the
machine's capacity (refer to the unit
electrical characteristics table ), near to
the machine.
Connection to the electrical network
must comply with current electrical
standards.
To carry out electrical connection:
Open the inspection panel which
allows access to the junction box. To
remove the inspection panel, extract the
controller from its support bracket .
Thread the power supply cable
through the cable guide provided on the
unit .
WARNING !
On site wiring must be carried out in
accordance with the wiring diagram
affixed to the unit's junction box.
The power cables for general power
supply to the unit must have a copper
core, and be dimensioned in
accordance with current IEC
standards.
The unit must be earthed via a
terminal block provided inside the
junction box.
The supply voltage must not vary by
more than 10%.Imbalance between
the phases must not be greater than
3%
All the connections are made on
screw terminals.
The wires should be stripped back 10
mm.
6.1-Electrical connection
Power supply
7-Electricity
12
7.1 The operation manual of the wire controller
Prg
mute
Sel
clear
1
2
3
4
Prg
mute
Button
Sel
Meaning
Pressing this button could returning back to the previous interface.
Function1
:
continually pressing this button could enter into the set interface.
Function2
:
pressing this button could enter into the next interface.
Function1
:
continually pressing this button could start the heating mode.
Function2
:
pressing this button could turn up and increase the value.
Function1
:
continually pressing this button could start the cooling mode.
Function2
:
pressing this button could turn down and increase the value.
1
)
About buttons
2
)
About icons
Ico
1;2
3;4
Meaning
Heating mode
Compressor1 and 2 start up
At least one compressor starts up
Condensate fan starts up
Defrosting
Electrical heater start up
Warning
Cooling mode
Ico
Meaning
Water pump starts up
CAREDL
μ
C SE
2
Compressor3 and 4 start up