3-Technical data

5

3.1 ELECTRICAL SPECIFICATION

Cooling: 

 temperature:35

/ 24

,Inter/outlet water temperature:12

/ 7

Heating: 

 temperature:7

/6

,Inter/outlet water  temperature:30

/35

Ambient 

Ambient 

4-Installation

6

200mm

800mm

500mm

500mm

400mm

400mm

4.1 Installation location

    

 The units are air cooled. Because of this, they must be installed outdoors in an area with 

sufficient clearance to provide free air circulation through the condenser coil. Any free air 
circulation restrictions will reduce the air flow, decrease the cooling capacity, increase the 
power input and, in certain cases, prevent the group from operating by excess condensation

 

pressure.
    It is prohibited to connect the helicoid  fan units to duct networks because of the pressure 
drops created by such networks. In the event that the unit is located in an area exposed to 
high wind, avoid the wind striking the fan surfaces directly. The arrows show the direction 
of air circulation through the unit (refer to diagram opposite).

4.2 Fitting the unit

     After installation, all sides of the unit must be accessible for regular maintenance 
operations.Removal of Panel 1 provides access to the electrical junction box, the 
compressor and the cooling circuit.
Note:
      Panel 1 is removable independently of the other panels and enables the unit to be run 
maintaining its normal operating characteristics. To disengage the panel after 
removal, extract the controller and its support bracket .

When  si

ght

ing  the  unit,  take  care  to  leave  sufficient  free  space  all  around  it  for  carrying  out 

maintenance.  The  minimum  free  distances  are  shown  and  must  be  adhered  to,  both  for  ensuring 
correction operation and for providing access.

Unit Model

Cooling Capacity

Heating Capacity

Cooling Power Input

Heating Power Input

Running Current(Cooling/Heating)

Power Supply

Compressor Quantity

Compressor

Fan Quantity

Fan Power Input

Fan rotate speed

Noise

Water Pump Input

Water  head

Water Connection

Water Flow Volume

Water Pressure Drop

Capacity Of  Water Storage

Unit Net Dimensions(L/W/H)

Unit Shipping Dimensions(L/W/H)

Net Weight

Shipping Weight

kW

Btu/h

kW

Btu/h

kW

kW

A

W

RPM

dB(A)

kW

m

inch

3

m /h

kPa

L

mm

mm

kg

kg

See package label

See nameplate

See package label

See the drawing of the units

HH8

7.1

24200

8.2

28000

2.5

2.0

10.9/8.7

230V~/50Hz

1

Rotary

1

120

850

56

0.2

8

1

1.4

17

23

Summary of Contents for Evo Control 8

Page 1: ......

Page 2: ...it 5 HYDRAULIC CONNECTIONS 5 1 Hydraulic connections 5 2 Connection of the chilled water loop 5 3 Drainniag 5 4 Treminal insulation 5 5 Starting operation 5 6 Saffety differencial pressostat 5 7 Hydraulic module 6 ELECTRICAL CONNECTION 6 1 Electrical connection 7 ELECTRICITY 7 1 7 2 7 3 7 4 Compensate temperature chart 8 MAINTENANCE 9 The operation manual of the wire controller The operation of th...

Page 3: ...must come in contact with the heat source or the fan rotating parts WARNING Preparation for shutting down the unit for a prolonged period if the installation does not contain glycol the evaporator and the chilled water pipes need to be carefully and completely drained of water Take care The unit should be handled using lifting and handling equipment appropriate to the unit s size and weight Take c...

Page 4: ...2 Description 3 2 1 DIMENSIONS 705 43 95 Top view 400 420 700 Models Evo Control 8 Front view 645 1015 Electric wire hole Water outlet 1 inch Drainage 1 2inch Water inlet 1 inch 479 ...

Page 5: ... letter with acknowledgement of receipt The manufacturer is not liable for physical damage to the unit after acceptance WARNING The sharp edges and surfaces of the coils can cause injury Avoid contact with them 2 3HANDLING THE UNIT Take care to avoid any sharp movements during the unloading and moving of the unit Do not push or pull it by any other means than its base Place a safety wedge between ...

Page 6: ...ressor Quantity Compressor Fan Quantity Fan Power Input Fan rotate speed Noise Water Pump Input Water head Water Connection Water Flow Volume Water Pressure Drop Capacity Of Water Storage Unit Net Dimensions L W H Unit Shipping Dimensions L W H Net Weight Shipping Weight kW Btu h kW Btu h kW kW A W RPM dB A kW m inch 3 m h kPa L mm mm kg kg See package label See nameplate See package label See the...

Page 7: ...d to high wind avoid the wind striking the fan surfaces directly The arrows show the direction of air circulation through the unit refer to diagram opposite 4 2 Fitting the unit After installation all sides of the unit must be accessible for regular maintenance operations Removal of Panel 1 provides access to the electrical junction box the compressor and the cooling circuit Note Panel 1 is remova...

Page 8: ... exchanger during handling and installation operations However it can create a risk of clogging with frost or ice on heat pump machines installed in cold or mountainous regions and exposed to the elements To avoid such a risk a shelter must be provided or the protective grill can simply be removed ...

Page 9: ...ts on the chilled water circuit 4 An adequate system to maintain water pressure in the circuit expansion tank or pressure regulating valve 5 Thermometers and pressure gauges installed on the exchanger inlet and outlet They will facilitate regular checks and maintenance 6 To avoid any risk of foreign bodies entering the system and to maintain optimum performance it is strongly advised to install th...

Page 10: ...s adequate to fill the installation 5 3 DRAINING Units are equipped with couplings to fill and drain the hydraulic circuit according to standards in force The water should come from a distribution network either to the unit directly or to any other point on the circuit linking the terminal units together 5 4 TERMINAL INSULATION In order to properly keep power consumption low and to comply with sta...

Page 11: ... DIFFERENTIAL PRESSOSTAT A safety differential pressostat is fitted as standard on the water inlet pipe into the evaporator in order to ensure adequate water flow to the evaporator before starting the unit It acts both in the event of partial blockage starting to take in ice and in the event of a drop in water flow due to pump failure This is the machine s main protection device 5 7 HYDRAULIC MODU...

Page 12: ...panel which allows access to the junction box To remove the inspection panel extract the controller from its support bracket Thread the power supply cable through the cable guide provided on the unit WARNING On site wiring must be carried out in accordance with the wiring diagram affixed to the unit s junction box The power cables for general power supply to the unit must have a copper core and be...

Page 13: ...ally pressing this button could start the heating mode Function2 pressing this button could turn up and increase the value Function1 continually pressing this button could start the cooling mode Function2 pressing this button could turn down and increase the value 1 About buttons 2 About icons Ico 1 2 3 4 Meaning Heating mode Compressor1 and 2 start up At least one compressor starts up Condensate ...

Page 14: ...y press Prg mute Sel clear CAREDL μ C SE 2 Continually press On the state of standby On the state of power on 2 Check the parameters On the state of power on or power off the measured temperature of B01 B04 could be checked Press or to enter into the temperature interface Press Up or Down to find the needed temperature then press to check it Press to return back to the previous interface B01 Inlet...

Page 15: ... of the unit Do not make any change of them when it is not necessary r01 r02 r03 r04 are permitted to set by the users For the default values please refer to Parameters Table The permitted setting are shown as below take r01 for example Sel Prg mute Sel Sel Sel Prg mute Sel clear 1 2 CAREDL μ C SE 2 Prg mute Sel clear CAREDL μ C SE 2 Prg mute Sel clear CAREDL μ C SE 2 Prg mute Sel clear CAREDL μ C...

Page 16: ...perature Heating temperature difference R02 R03 R04 2 40 2 1 4 Malfunction When there is something wrong with the unit the wire controller will display the error code according to the fault reason For the detailed meanings of the error codes please refer to the Fault Table For example Prg mute Sel clear CAREDL μ C SE 2 Water inlet fault ...

Page 17: ...he screw terminal block every 6 months CONDENSER COILS The condenser coils do not require any special maintenance except when they are clogged by paperor any other foreign bodies In corrosive atmospheres providefor suitable protection Cleaning is by washing with detergent and water at low pressure and then rinsing with clean water EVAPORATOR The direct expansion evaporator comprises a tube in tube...

Page 18: ...oduct at the end of its useful life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This product is compliant with directive 2002 95 EC RoHs concerning restrictions for the use of harmful substances in electric and electronic device...

Page 19: ... line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm 2 mm 25 2 mm 25 2 35mm 2 50mm 2 70mm 2 95mm 2 Three phase unit 2 3 1 5mm 2 3 2 5mm 2 3 4mm 2 3 6mm 2 3 10mm 2 16mm 3 2 25mm 3 2 3 25mm 2 3 35mm 2 3 50mm 2 3 70mm 2 3 95mm 30mA less than 0 1 sec 30mA ...

Page 20: ...Code 20170517 0001 ...