Operation Guide
Thermostat Operation
Minimum Run Time (MRT)
The thermostat has a Minimum Run Time
after the start of any heating or cooling call.
This minimum run time assures even heating
and cooling cycles. The MRT delay will keep
the system on even if reaches setpoint or you
change the setpoint to a temperature that
would satisfy the call, until the MRT expires.
Changing the Mode to OFF will cancel the
MRT and the system will turn off immediately.
The MRT can be adjusted in the Installer
Settings menu of the thermostat.
Note: The MRT status is shown in the
thermostat System Status on-screen labels.
Minimum Off Time (MOT)
The thermostat has a Minimum Off Time after
any heating or cooling call is finished. This
delay prevents rapid heating/cooling cycles
and also provides “short cycle protection” for
compressor calls. This delay may be
noticeable when you change a setpoint and it
does not respond immediately due to another
call that has recently completed and the MOT
delay timer is preventing the system from
restarting. The MOT delay time can be
adjusted in the Installer Settings menu of the
thermostat. There is a minimum of 5 minutes
delay to assure compressor protection.
Note: The MOT status is shown in the
thermostat System Status on-screen labels.