Page
20
1. With the filter tank in its installed location, use a 1/2 inch carbide drill bit and drill a 6 inch-
deep hole in the floor. There should be a total of 6 1/2 inches depth from the top of leg
plate.
2. Remove all debris from the holes.
3. Assemble washer and nut, leaving top of the stud exposed above the nut. Drive anchor into
the hole until the washer is flush.
4. Expand the anchor by tightening nut 3-5 turns past the hand tight position, or torque to 55
ft-lbs.
Auxiliary Equipment Installation
Gauge Panel
Bolt the gauge panel to mounting plate with four 1/4 x 1 inch screws, washer, and nuts
(included).
Figure 3: Gauge Panel
Pressure Gauges
All gauges supplied by Neptune-
Benson™ are designed with dampening orifice openings to
minimize damage due to surges or quick changes in pressure. The small opening is subject to
clogging, especially on gauges that are located before the filter.
If a gauge reacts slowly to changes in pressure or tends to remain at an elevated pressure while
the system is shut down, remove the gauge for inspection. The opening or orifice is located
1/4 x 1 inch screws,
washers, and nuts
(included)
*Differential pressure
transducers
1/4 inch OD tubing
(included)
1/4 inch male compression
connection (included)
1/4 inch ball valve
(included)
1/4 inch FPT X. FPT
threaded tee
Summary of Contents for DEFENDER SP-27-48-487
Page 14: ...Page 14 General Installation Schematic ...
Page 15: ...Page 15 DIMENSIONAL REFERENCE Standard Defender ...
Page 16: ...Page 16 Assero Defender Reduced Height Defender ...
Page 17: ...Page 17 Reduced Height Defender ...
Page 77: ...Page 77 APPENDIX ...
Page 78: ...Page 78 Electrical Schematic ...
Page 79: ...Page 79 Head Loss Curve ...