Page
44
18.
Tank Drain Option (Auto Drain Valve
Open to flush tank bottom)
OFF
19.
Tank Drain On Time
5 Seconds
Time that the valve is open.
20.
Precoat Line Option (Auto Valve to
allow make up water for TDS
control)
OFF
21.
Precoat Line On Time
5 seconds
Time that the valve is open.
22.
UV Screen Cycle Option (Automatic
UV Screen)
OFF
Set to
ON
if the option is used.
23.
UV Screen Cycle Time
0 hours
If on, set to the desired time for self-
cleaning.
24.
Water Level Enable
OFF
If set to
ON
, probes and sensing
chamber are required for water level
control.
25.
Water Level Fill Delay
0 seconds
Set to the required time from when the
water level reaches the hi level probe
to the desired optimum water level.
26.
Level Stabilize Delay
5 seconds
27.
Level Valve Max Open Time
50 seconds
To prevent overfilling the pool, this is
the maximum time that the solenoid
valve is open during fill.
28.
VFD Display Enable
OFF
To utilize this feature, interlock wiring
is required from VFD to D7.
29.
VFD Units
GPM
Other available units of measurement
include
m
3
/hour
and
l/second
.
30.
Low Pressure Cutoff
50 PSI
Low air pressure limit. Never operate
the filter with this parameter disabled.
31.
Delta-P Difference Value
12 PSI
If enabled, the filter automatically
bumps when a pressure differential
reaches 12 PSI, unless the bump block
is scheduled.
32.
Flow Rate Enable
OFF
Use this for a 4
–20 mA flow sensor
when you do not have a VFD.
33.
Flow Units
GPM
Other available units of measurement
include
m
3
/hour
and
l/second
.
34.
Output Log Frequency (minutes)
OFF
35.
Precoat Pump Enable
OFF
Set to
ON
when a separate precoat
pump is used.
36.
Main Pump On to Effluent Open
Delay
6 seconds
Time that the main filtration pump is on
before the effluent valve opens.
37.
Precoat Pump Off after Regen Close
Delay
5 seconds
Time that the precoat pump is on
before the valve closes.
38.
Dual Mode Option
OFF
This parameter is for industrial use
where two filters alternate filtration.
39.
Main Drain Delay - Dual D4
0 seconds
40.
Language
English
Other available languages include
German
,
Chinese
,
Spanish
, and
French
.
41.
Pressure Units
PSI
Other available units of measurement
include
BAR
and
KPI
.
Summary of Contents for DEFENDER SP-27-48-487
Page 14: ...Page 14 General Installation Schematic ...
Page 15: ...Page 15 DIMENSIONAL REFERENCE Standard Defender ...
Page 16: ...Page 16 Assero Defender Reduced Height Defender ...
Page 17: ...Page 17 Reduced Height Defender ...
Page 77: ...Page 77 APPENDIX ...
Page 78: ...Page 78 Electrical Schematic ...
Page 79: ...Page 79 Head Loss Curve ...