E-80-136KTL User Manual
Copyright ©EVOLVE ENERGY GROUP CO.,LTD
- 40 -
incorrect is not included in the warranty.
Figure 5-2 Recommend DC cable size
Copper cable cross section area
(
mm
2
)
Cable OD (mm)
Range
Recommend
4.0~6.0
4.0
4.5~7.8
Step1: Find the metal contact pins in the accessories bag, connect the cable
according below diagram (1. Positive cable, 2. negative cable)
;
Figure 5-8 DC cable connection
(
1
)
Step 2: Crimp the PV metal contact pin to the striped cable using a proper crimping
pliers.
Step 3: Insert wire into the connector cap nut and assemble into the back of male or
female plug, when you heard a “click”, the pin tact assembly is seated correctly. (3.
Positive Connector, 4. negative connector)