E-80-136KTL User Manual
Copyright ©EVOLVE ENERGY GROUP CO.,LTD
- 31 -
*take picture as reference
No
Name
Description
A
DC input
terminals
PVX+/PVX-
PV connector
B
USB/WIFI port
USB/WIFI
For WIFI, GPRS Communication
C
RS485
Modbus/DRMs
RS485/DRMs
RS485 Communication port/
DRMs port
D
AC output
terminals
AC output terminal
E
Grounding
Connecting terminal of the
ground, choose at least one for
grounding connection
5.3.
Grounding Connection (PE)
Connect the inverter to the grounding electrode using ground cable
E- 75-136kW is a transformer less inverter which requires the positive
pole and negative pole of the PV array are NOT grounded. Otherwise, it will
cause inverter failure. In the PV system, all non-current-carrying metal parts
(such as mounting frame, combiner box enclosure, etc.) should be connected
to earthed.
Note
Preparation: prepare the grounding cable (recommend 16mm
²
yellow-green
outdoor cable and M8 OT Terminal)