background image

EWC Controls Inc.   385 Highway 33    Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362      E-Mail- info@ewccontrols.com

2

BYPASS SIZING CALCULATIONS

BYPASS SIZING CALCULATIONS

The bypass damper must be installed horizontal & level between the supply duct and the return duct.

Position the damper to open in the direction of airflow back to the return duct or into a conditioned area.

Place the duct connection on the return so that the bypass air has a minimum 6 feet of return duct. before it 

enters the air handler, if space permits. 

If a Restricting Hand Damper is installed, it should have been setup 

already. If not, refer to Application note 090376A0169D. Otherwise, close the hand damper ½ way.

Position the ARM in the “IDEAL ARM LOCATION” for the correct direction of air flow and tighten the 

thumb screw.  (Refer to page 4)

Position the 

Extra Weight (optional)

 high up on the ARM and tighten the thumb screw. Position 

Weight#1 

towards the bottom of the arm and tighten the thumb screw. (Refer to page 3)

Energize 

ALL

 Zones to operate the unit with the Fan running on the Highest speed. (Usually a Cooling 

demand, 2nd stage if applicable) 

Return to the damper & confirm that the by-pass damper is closed. If necessary, reposition the 

Extra Weight 

or Weight #1

 lower on the ARM until the damper closes completely.  (It should be closed to the point where 

any additional force will start to open it) (Refer to page 3)

Turn off all Zones but the Smallest Zone & Wait about 45 seconds.

Monitor the airflow for the Smallest Zone.

  Is there to much Airflow or Noise?  Proceed to 

Step 9

.

Is there Insufficient Airflow?  Proceed to 

Step 10

.

Is the Airflow Acceptable?  Proceed to 

Step 11

.

Excess Velocity:  

Reposition the 

Extra Weight

 higher up on the ARM until the velocity in the smallest zone 

has subsided to an acceptable level.  If the velocity remains high, reposition 

Weight #1 

higher up on the arm, 

or if necessary, reposition the ARM closer towards “6 or 0” on the scale. 

(Depending on the model).

 

Insufficient Velocity:  

Reposition the 

Extra Weight

 lower on the ARM until the velocity is at an acceptable 

level.  If the velocity remains low, reposition the ARM closer towards the “3 or 9” on the scale (

(Depends on 

model. Refer to page 3&4) 

depending on direction of flow). If velocity still remains low for the smallest zone, to 

much air is being forced through the barometric damper. You can order additional weights or you should 

consider installing an Electronic By-Pass Damper (Model EBD).

Congratulations, your PRD By-Pass damper is now properly adjusted.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

BAROMETRIC BYPASS SET-UP PROCEDURE

BAROMETRIC BYPASS SET-UP PROCEDURE

Start with the system’s Total Cfm (2000Cfm) 3 zone system (Zone 1 = 750Cfm, Zone 2 = 750Cfm, Zone 3 = 500Cfm plus 4 open runs @ 50Cfm)

Calculate the Cfm for the smallest zone that can run by itself (500Cfm)

Calculate the Cfm for any non-dampered (open) duct runs (4 x 50Cfm = 200 Cfm)

Calculate Damper stop leakage (20%) on both inactive zones (750cfm x .20 = 150 x 2 = 300Cfm)

Subtract all values from total Cfm (2000 - 500 - 300 - 200 = 1000 Cfm bypass flow) 

The left over amount is the bypass Cfm.  Refer the bypass Cfm to the chart on Page 1, match to the closest size. If you don’t have enough room for 

that size, then go down one size. By-pass velocity will increase on smaller bypass ducts. 

Regardless of the bypass size, consider installing a 

Restricting Hand Damper after the Bypass damper, in order to set sufficient differential pressure and control how fast the bypass air mixes with 

the return air. (See graphic on page 1)

EXAMPLE:

  

5 ton system @ 400 Cfm Per ton = 2000 Cfm

             

 2000 Cfm

Subtract Smallest Zone = 500 Cfm

           

 -500 Cfm

Subtract Damper Stop Leakage = 300 Cfm

 -300 Cfm

Subtract Open Runs = 200 Cfm

   

 -200 Cfm 

      

            

1000 Cfm

                                

1000 Cfm @1400Fpm = 12x10 PRD

or

                                                                                                                                                1000 Cfm @ 900 Fpm = 20x10 PRD

1.

2.

3.

4. 

5.

6.

Summary of Contents for PRD

Page 1: ...ypass flow is achieved See Page 2 for details For field versatility the hex shaped arm can be inserted into either side of the damper Additional weights can be added if necessary The barometric by pass damper is installed in the duct work to regulate excess air pressure and volume The damper can be mounted to relieve pressure by returning the air back to the return air duct or by dumping it into a...

Page 2: ...cceptable level If the velocity remains high reposition Weight 1 higher up on the arm or if necessary reposition theARM closer towards 6 or 0 on the scale Depending on the model Insufficient Velocity Reposition the Extra Weight lower on the ARM until the velocity is at an acceptable level If the velocity remains low reposition theARM closer towards the 3 or 9 on the scale Depends on model Refer to...

Page 3: ... 5 6 7 8 9 POSITION ARM IN IDEAL LOCATION IF AIR FLOW IS IN DIRECTION INDICATED BY THE ARROW ABOVE I D E A L A R M L O C A T I O N I D E A L A R M L O C A T I O N AIRFLOW AIRFLOW POSITION ARM IN IDEAL LOCATION IF AIR FLOW IS IN DIRECTION INDICATED BY THE ARROW ABOVE ARM GRADUATED ADJUSTMENT SCALE THUMB SCREWS IDEAL ARM LOCATION WEIGHT 1 EXTRA WEIGHT I D E A L A R M L O C A T I O N AIRFLOW POSITION...

Page 4: ... LOCKING COLLAR OVER DAMPER SHAFT 3 INSERT HEX ARM INTO DAMPER SHAFT 4 ALIGN LOCKING COLLAR THUMB SCREW WITH ONE OF THE 4 HOLES ON THE DAMPER SHAFT WHILE HOLDING ARM AT THE DESIRED ANGLE 5 TIGHTEN THUMB SCREW TO SECURE HEX ARM IN PLACE 6 POSITION WEIGHT ON HEX ARMAND TIGHTEN THUMB SCREW TO SECURE IN PLACE 7 REFER TO PAGE 2 FOR SET UP PROCEDURE THUMB SCREW LOCKING COLLAR DAMPER SHAFT HEX ARM FIGURE...

Reviews: