EWC Controls Inc.   385 Highway 33    Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362      E-Mail- info@ewccontrols.com

7

HK2000
LED’s

The HK2000 is equipped with 7 LED’s which indicate system operation and status. Familiarize 
yourself with the LED’s definitions, in order to quickly determine the system status and mode of 
operation. 

ECONOMY

RED

FAN

RED

COMPRESSOR

RED

COOLING CALL

RED

OA TEMP MODE

GREEN

FRESH AIR MODE

GREEN

ENTHALPY MODE

GREEN

Economy LED illuminates when panel has activated all dampers to the Outside Air Mode,
Fresh Air Mode, Enthalpy Mode, or Mechanical Assistance Mode.

Compressor LED illuminates when panel has activated the Mechanical Cooling or 
Mechanical Cooling Assistance.

Fan LED illuminates when the panel has activated the Indoor Fan Blower.

Flashes in unison with Fresh Air & Enthalpy LED’s to indicate System Status. Illuminates
when Outside Air Temperature is suitable for Economy Operations.

Flashes in unison with Outside Air & Enthalpy LED’s to indicate System Status.
Illuminates when a scheduled Fresh Air Cycle is active.

Flashes in unison with the Outside Air & Fresh Air LED’s to indicate System Status.
Illuminates when the Enthalpy control or other external device has closed it’s 
contacts.

Cooling Call LED illuminates when the panel detects a cooling demand from the 
Thermostat.

NOTE:

 It is possible to observe both the Economy LED and the Compressor LED illuminated at the same time.

EXAMPLE 1:

 A call for cooling has occurred but outdoor conditions are not suitable to satisfy the demand, so the 

compressor is activated and the Compressor LED illuminates. The Fresh Air Cycle Schedule activates the dampers to 
the Fresh Air Mode to satisfy fresh air requirements, so the Economy LED will also illuminate. 

EXAMPLE 2: 

A call for cooling has occurred but outdoor conditions are not suitable to satisfy the demand, so the 

compressor is activated and the Compressor LED illuminates. The Mechanical Assistance Feature activates the 
dampers to the Fresh Air Mode to assist the compressor, so the Economy LED will also illuminate. 

A Return and Outdoor Air Sensor is required in order to utilize the Mechanical Cooling Assistance Feature.
The Fresh Air Cycle Schedule operates independent of all other functions, and regardless of outside temperatures. 

EC

ON

OM

Y

FA

N

CO

MP

RE

SS

OR

CO

OLI

NG

 C

ALL

OA

 TE

MP

 M

OD

E

FR

ES

H A

IR M

OD

E

EN

TH

ALP

Y M

OD

E

ON

OFF

ON

ON

OFF OFF OFF

ON

ON

ON

OFF

OFF OFF ON

ON

ON

ON

OFF

OFF

OFF ON

ON

ON

ON

ON

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

MECH. ASSISTED COOLING

MECH. COOLING CALL

ENTHALPY MODE

OUTSIDE AIR MODE

FRESH AIR MODE

BASIC MODE LED INDICATIONS

Summary of Contents for ULTRA-ZONE HK2000

Page 1: ...reaker is tripped it will get quite hot To reset the breaker remove the 24vac power Locate and repair the short Then restore the power See Page 9 Compatible HVAC Systems Compatible Thermostats Operating Power Thermal Circuit Breakers EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 E Mail info ewccontrols com Model HK2000 Fresh Air Economy Control System TB 214 P ...

Page 2: ... Cycle Setting is changed 0 2 4 6 8 10 12 FRESH AIR CYCLES HOUR Adjustable Outside Air Sensor The HK2000 includes a reliable 10K Thermistor Sensor The sensor must be mounted outdoors and wired back to the panel It provides the processor a means of reading the outside dry bulb temperature Used with OA Temp Mode and Mechanical Cooling Assistance Optional Return Air Sensor Required for Mechanical Ass...

Page 3: ...ROLS INC Englishtown NJ THERMOSTAT SYSTEM TRANSFORMER HEAT RELAY W COOL RELAY Y FAN RELAY G R C G R Y W C RETURN AIR SENSOR OPTIONAL USED ONLY IF MECHANICAL COOLING ASSISTANCE IS REQUIRED MA ND URD 6 4 1 M M C NO NC M M C NO NC MA ESR POWER CLOSE SPRING OPEN MA ESR POWER OPEN SPRING CLOSE OUTSIDE AIR SENSOR WIRING DIAGRAM FRESH AIR ECONOMIZER Model HK2000 Control Panel DRY BULB CONTROL MODE SEPARA...

Page 4: ... Outside Air Mode Free Cooling If the HK2000 detects that the Enthalpy control has opened it s contacts The HK2000 will terminate economy operation and energize mechanical cooling to satisfy the cooling demand All dampers default back to the Return Air Mode unless a Fresh Air Cycle occurs at the same time NOTE Follow the instructions when installing and setting up the Enthalpy control It should be...

Page 5: ... FRESH AIR MODE ENTHALPY MODE COOLING CALL BYPASS RUN O A TEMP R A TEMP ENTH ALPY C Y R G M6 M4 M2 M1 RM CM M6 M4 M2 M1 M6 M4 M2 M1 SYSTEM THERMOSTAT HK2000 ECONOMIZER FRESH AIR SYSTEM EWC CONTROLS INC Englishtown NJ THERMOSTAT 1 2 3 ENTHALPY CONTROL MODEL EC H705 A B D C G R Y W C WIRING DIAGRAM FRESH AIR ECONOMIZER Model HK2000 Control Panel ENTHALPY CONTROL MODE 42 48 54 60 66 72 78 DRYBULB ECO...

Page 6: ... Mode ReturnAir Damper OPEN DEFAULT OutsideAir Damper CLOSED ExhaustAir Damper CLOSED OUTSIDE Air Mode Return Air Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN FRESHAirMode ReturnAir Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN MECHANICAL ASSISTANCEMode Return Air Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN Warning Your application may limit the dampers...

Page 7: ...s Cooling Call LED illuminates when the panel detects a cooling demand from the Thermostat NOTE It is possible to observe both the Economy LED and the Compressor LED illuminated at the same time EXAMPLE 1 A call for cooling has occurred but outdoor conditions are not suitable to satisfy the demand so the compressor is activated and the Compressor LED illuminates The Fresh Air Cycle Schedule activa...

Page 8: ...s OFF A setting of 12 is continuous fresh air Example A single hour is divided into Five 5 minute increments of fresh air The installer has chosen a setting of 6 cycles per hour which results in a total of 30 minutes of fresh air every hour The HK2000 will activate the dampers into the Fresh Air Mode for 10 minutes the 1st qtr Hour 5 minutes the 2nd qtr Hour 10 minutes the 3rd qtr Hour and 5 minut...

Page 9: ...he life of your standard return air filter 4 Use hooded intake and exhaust fittings to stop rain or snow from falling into your duct 5 DO NOT install a return air damper or completely close off a return air damper if your fresh air duct is under sized or completely closed off Example Return air main is 20 x25 and you install an 8 round fresh air duct damper You will NOT install a return air damper...

Page 10: ..._______________________ Dampers not responding and HK2000 LED s are on ______________________________ ISOLATING 24vac SHORTS ____________________________ F2 circuit breaker protects the HK2000 and reacts to a short in the thermostat field wiring ______________________________ F1 circuit breaker protects the HK2000 and reacts to a short in a damper motor or the damper motor field wiring SYMPTOMS __...

Page 11: ...on to terminal 1 and 24vac hot to terminals 2 and 4 Damper should Open Remove 24vac hot from terminal 4 Damper should Close BMD SMD ND URD Dampers Connect 24vac common to terminal 1 and 24vac hot to terminal 4 Damper should Open Remove 24vac hot from terminal 4 and apply to terminal 6 Damper should Close SR ESR Power Close Spring Open Dampers Connect 24vac common hot to the two motor M terminals D...

Page 12: ...UTSIDE AIR SENSOR Model HK2000 Fresh Air Economizer Control Panel NOTE This diagram reflects Dry Bulb Mode Diagram also applies to Enthalpy Mode SEPARATE T40 VA 24 VAC 40VA T FORMER 42 48 54 60 66 72 78 DRYBULB ECONOMY CHANGEOVER TEMP 0 2 4 6 8 10 12 FRESH AIR CYCLES HOUR Set to desired Outdoor Changeover Temperature Set to desired number of Fresh Air Cycles Y2 W2 2 STAGE GAS or ELECTRIC FURNACE W...

Reviews: