1. Low temperature zone temperature settings: Press         displays the 

temperature of low temperature zone, press         or         to change the 

controlling temperature. Without pressing any key when finished operating

it 

will automatic save memory setting parameters after six seconds.

2.Parameter setting: Holding          and          after six seconds to enter Setup, 

the corresponding indicator flashes, more than once every press         to run the 

next function indicators, then press          or         to change the parameters for 

each function. Without pressing any key when finish operation, it will 

automatic save memory setting parameters after six 

seconds.

C ode

M801AH.15.08.18

Microcomputer Thermostat Serial

EW-801AH 

Directions

   This product is mainly used in solar water heater equipment, the use of

 the temperature difference and temperature to control the output. This

 product has two-ways output control, one way to control the temperature

 difference between the two temperature zones, when the temperature

 difference reaches the set value, automatically run the pump cycle, the 

temperature of the two temperature zones to reach equilibrium, another 

way to control electric heating; when solar heating fails reached (low 

temperature) set temperature, the electric heating system is heated 

to a set temperature automatically start and automatic temperature control 

range values ​​within a temperature difference.

 

1

AC220V   

±

10

   50HZ/60HZ

2

5A/220V/AC

3

: ≤

3W

4

-10

℃ ~

50

    RH

90

5

Control

 

of

 

heating

2

℃~

99

6

Control

 

of

 

thermal

 

start

-

up

3

℃~

50

7

Resolution

1

         

Accuracy

:±

1

8

nput signal

two

-

ways

 

sensors

20KX

1.5m

X2

9

76(L)

×

35(H)

×

76(D)mm

10

Hole Size

71(L)

×

29(H)mm

Operating voltage

Load

Power Consumption

Working environment

Overall Dimension

Output

 

Panel Diagram

Display the current temperature of 
the low temperature zone

Running lights

1.The voltage must accord with controller's demand.         

The voltage's deviation  is no more than 

±

10%.

2.The loop of sensor is possible to keep away from the

loop of power.

3.The sequence of line's  must have been connected

    Properly.

When two temperature sensor detects a 
temperature of two zones, the difference is greater 
than the value of thetemperature difference 
between the set start value, the circulation pump 
relay ON, temperature difference setting range: 
temperature of the pump 1 

 ~ 50 

℃.

Temperature difference between the started

Temperature hysteresis

After reaches the set  point and stop 
heating, temperature down, and then 
restart the difference between electric 
heating, temperature hysteresis setting 
range: 1 

 ~ 20 

℃.

High temperature zone temperature correction

Low temperature zone temperature correction

When the thermostat detects the 
temperature of the high temperature 
zone and the actual value error, this 
feature can be amended. Correction

 

range: -10 

 ~ 10 

℃.

When the thermostat detects the 
temperature of the low temperature 
zone and the actual value error, this 
feature can be amended. Correction

 

range: -10 

 ~ 10 

℃.

Sensor error self-test function

When the high temperature zone 
sensor circuit or open circuit 
will show 

"EH"

 symbol.

When the low temperature zone 
sensor circuit or open circuit will 
show 

"EL"

 symbol.

E W - 8 0 1

EW-80 1

E W- 80 1

EW- 80 1

EW-801

E W- 801

EW-80 1

E W- 801

 

Temperature difference of  the pump stopped

When the temperature difference between the two 
sensors is less than this value, the circulation pump 
stops, Range 1 

 ~ started temperature difference-1 

℃。

Note: When difference of the pump stops setting “0”, 
once the circulation pump relay ON, circulation 
pump not stopped.

Technical Specifications

Demand of install

Brief on Controlling Procedure

Ewelly

Ewelly

Ewelly

Ewelly

Ewelly

Ewelly

Ewelly

Ewelly

In the non setting state, press        can  see the current 
temperature of the high temperature zone.

E W- 80 1

Heating temperature difference

High temperature zone must be 
higher than the setting temperature  
difference. Equal or less than this 
value automatically start heating 
control. Heating temperature 
range:0

℃~

20

℃。

E W-801