Functional characteristics
TIG welding
26
099-00T404-EW501
02.07.2020
5.1.6
Average value pulse welding
Once the pulse function is activated, the red signal lights for the main current AMP and secondary current
AMP% light up at the same time. Average value pulsing means that the system switches between two
currents periodically, an average current value (AMP), a pulse current (Ipuls), a balance (
) and a fre-
quency (
) having been defined first. The predefined ampere current average value is decisive, the
pulse current (Ipuls) is defined by the
parameter as a percentage of the average current value (AMP).
The pulse pause current (IPP) is not set; the machine control calculates the value instead to ensure that
the average value of the welding current (AMP) is maintained. For average value pulsing, the
current
is the secondary current only, activated with the torch trigger.
Figure 5-15
AMP = main current (average value), e.g. 100 A
Ipuls = pulse current =
x AMP, e.g. 140% x 100 A = 140 A
IPP = pulse pause current
Tpuls = duration of one pulse cycle = 1/
, e.g. 1/100 Hz = 10 ms
= balance
Selection
Figure 5-16
Pulse current
Figure 5-17