background image

Parameter

Power up
Response
Off Delay
On Range
Off Range
1st Zone
2nd Zone
3rd Zone
4th Zone
Corridor 1
Corridor 2
Global 1 Rx
Global 2 Rx
Passive Photocell
Manual Input
Start Lamps
Entry Scene
Bright-Out
Fade to Of*
Vacant
Dimming
Set-Point Low
Set-Point High 

Default
Setting

ON
AUTO
20 min
20
100%
-
-
-
-
-
-
NO
NO
YES
LOCAL
MAX
1
NO
NO
OFF
100%
766
1022

Options

ON/OFF
Auto/Semi-auto
1min-96hrs or Disabled
1-100
10-100% in 10% increments
A

1-100 

A

1-100 

A

1-100

Address 1-100
1-100 Building Address Span
1-100 Building Address Span
YES/NO
YES/NO 
YES/NO
LOCAL/SHARE
MAX/MIN
1-6
YES/NO
YES/NO
10 Exit Scenes
Regulate 50-100%
0-1023
0-1023

ddress 
ddress 
ddress 

Options

Each of these settings
can be re-programmed,
if desired, by use of the
infrared programming
tool HP2000.

- Manual Input is only
  available via the
  Wireless OneSwitch 
  facility of the 
  MLS2500DWL(F) and
  MLS2500DALIWL(F).
  See Application Note
  AN4021 for further
  information

Commissioning

The units are supplied with the factory default settings, shown below, which render commissioning, apart from 
zoning, unnecessary in many applications.  To allocate to zone(s), effected via the MLS Bus signals, and make use 
of the programmable settings, an infrared commissioning tool is required (the HP2000).  A ten-second time delay is 
selectable to aid commissioning. 

Sensitivity to Movement

While the factory

Factory Default Settings

 settings will be correct for many applications, the sensitivity can be adjusted if required.  

ON Sensitivity (ON Range):

 This sets the detector’s range when the lights are ON.   Choose setting from 1-100 

where 1 is lowest and 100 is maximum.  (Note: Choose the lowest level possible to give adequate detection.)

OFF Sensitivity (OFF Range):

 This sets the detector’s range when the lights are OFF.  Choose % setting from 10% 

to 100% where 10% = 10% of ON Sensitivity and 100% = same as ON Sensitivity.   This is an approximation and 
should be tested on site during commissioning. 

Like all programmable parameters, the sensitivity settings will be retained in the event of a power failure and can be 
re-programmed any number of times.

Setting the Photocell

The regulating light level is set using either a hand-held controller (HC5) or via the infrared programmer HP2000. 

i)  Regulating Only

Using a light meter, set the required light level and choose Set Light Level in the USER REMOTE menu on the 
HP2000. A snapshot of the current conditions is taken by the detector and stored as the regulating set point -                   
Set-Point Low in the table above. When used with regulating ballasts, the photocell may hold lights off upon entry 
should sufficient natural light be available. It will only turn lights off in an occupied area if Bright-Out is set to YES and 
the light level exceeds the Set-Point High setting for a period.

Please  note  that,  although  configurable  as  a  regulating  photocell,  providing  closed-loop  dimming  according  to 
daylight levels, it is probable that the typical corner-of-room location dictated by the needs of the presence detection 
function will compromise the detector's ability to achieve precise light levels on the working plane, due to the effects 
of strong 

     

reflections of light of all origins from the walls and/or of direct daylight from any windows in its field of view. 

Fixing 

                                                  

            

1.  The Digital Mid Range LightSpot is an extremely sensitive movement detector; it is essential therefore that it 

be installed on a rigid surface that will not itself be subject to any movement or vibration.

2.   Before isolating the circuits to be switched, check that all lighting is fully operational and that there is no moving 

equipment or machinery within the monitored area which may cause nuisance switching.

3.   Position the detector where it has a good forward “view” of the area to be controlled.  Ideal mounting location is 

normally in a corner by the entrance or at one end of a corridor at a height of 2.5 to 4m.  Do not mount within 
25cm of a fluorescent fitting. 

4a. 

MLS2500D - Surface version

Separate the detector from its back-box by loosening the locking screw so that approximately 3mm of thread is 
visible and then twisting the detector off the back-box.  Note the arrow symbol moulded into the bottom of the 
back-box.  The fixing holes allow for mounting on a BESA box or direct to a rigid surface.  Secure the back-box 
firmly to a rigid surface so that the arrow points into the controlled area.

4b. 

MLS2500DF- Semi-flush version

Use a hole saw to drill a 76mm hole into the ceiling tile.  The flush ring is designed to clamp the tile between its 
two halves.  Loosen the locking screw so that approximately 3mm of thread is visible and remove the bottom 
half of the flush ring.  With the detector in the ceiling, pointing towards the area to be controlled, fit the bottom 
half of the flush ring to the assembly.  Depending on the thickness of the ceiling tile, screws longer than those 
supplied may be required to hold the two halves of the flush ring together.  

It is recommended that Mid Range detectors be ceiling mounted. Where this is not possible, the wall-mounting kit 
(WMK - see cover page)  must be used.

Only suitably qualified personnel should install this equipment.

Please note that this product uses microwave technology to detect occupancy and is not recommended for 
applications where there are large areas of metal, e.g. metal ceiling or panelling, as unpredictable sensitivity 
may result. 

Also, microwave presence detection is not completely attenuated by materials such as plasterboard, wood and 
glass, so the possibility of unwanted presence detection through office partitions should be considered when 
determining detector positioning and sensitivity settings within the intended application. 

Electrical Connections

Digital Mid Range LightSpot should be connected in accordance with the diagram below
Digital Mid Range LightSpot is designed to control up to 25 DSI or DALI ballasts, a switched load of up to 10 Amps or 
a combination of the two. When controlling DSI or DALI ballasts the ballast types must not be mixed. The DSI or 
DALI input terminals on the ballasts should be connected in parallel with each other and to the Polarity-Free Digital 
Output terminals of the MLS2500D. Each DSI or DALI luminaire is controlled completely by its digital input and 
therefore would normally have a permanent power supply. Turning the power off to some lights within a control circuit 
will not affect the operation of those lights that remain powered and under the control of the MLS2500D. 
When switching via the relay output, multiple MLS2500Ds' relay outputs may be connected in parallel provided the 
controlled  load  does  not  exceed  10 Amps.  If  digital  ballasts  are  also  being  controlled,  the  digital  outputs  from 
different detectors must never be connected one to another, even if they are of the same type. 

 

L

L

N

1

2

3

4

5

6

D

7

8

M

D

M

(M

LS

 B

us

)(

Di

gi

ta

l O

ut

)

S

W

W4364A

Digital Mid Range LightSpot 

Always check product label before wiring

Live Out

Live In

Neutral

Earth

D1

D2

MLS 1

MLS 2

Mains
Supply

Live

Neutral

Earth

10 Amps Maximum

SWITCHED LOAD

MLS 2-core Bus Cable

Do NOT connect to Mains

Note: 

A means of disconnection must be incorporated into the fixed wiring in accordance with the current wiring regulations.

Digital Dimming Signal Pair to Ballasts