Technical Data 

   

OPERATING VOLTAGE: 24V AC/DC
POWER CONSUMPTION: <0.5W
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m 
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height

DEPTH REQUIRED BEHIND CEILING: 125mm
WEIGHT: 70g excluding cable 
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: 4X
SW OUTPUT: Gold contacts for signal only (0.5A @ 24V ac/dc)
BALLAST CONTROL: Up to 25 analogue or digital ballasts

115mm

65mm

Ballast Type

Non-Dimming ON

ON

ON

ON

1-10V 

ON

ON

ON

OFF

DSI

OFF OFF ON  OFF

DALI

OFF OFF OFF  OFF

     1

  2

  3

  4

DIL Switches 

W4062G

Installation and Commissioning

Instructions

Note: HP10 or HP2000 required for commissioning

 MS1224UF

Silver Series Regulating LightSpot

24V AC/DC Operation

Electrical Connections

Red   

Black 

24V AC/DC

Supplied pre-wired to  
the following plugs:

Metway GSK86502

Volt-free 

output

Ballast 

control

          
Green    -      

White          
Blue            

Black 

White 

Green 

Red 

Yellow 

          
Blue            

Wieland 25.380.3353.0

Ex-Or 

Haydock Lane, Haydock, Merseyside WA11 9UJ

Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 272767  
Email: technicalsales.ex-or@honeywell.com