Technical Data
OPERATING VOLTAGE: 24V AC/DC
POWER CONSUMPTION: <0.5W
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3.0m
RANGE: Cone-shaped detection pattern, diameter (at floor level) = 2.4 x mounting height
DEPTH REQUIRED BEHIND CEILING: 125mm
WEIGHT: 70g excluding cable
COLOUR: White
MATERIAL: Flame retardant PC/ABS
IP RATING: 4X
SW OUTPUT: Gold contacts for signal only (0.5A @ 24V ac/dc)
BALLAST CONTROL: Up to 25 analogue or digital ballasts
115mm
65mm
Ballast Type
Non-Dimming ON
ON
ON
ON
1-10V
ON
ON
ON
OFF
DSI
OFF OFF ON OFF
DALI
OFF OFF OFF OFF
1
2
3
4
DIL Switches
W4062G
Installation and Commissioning
Instructions
Note: HP10 or HP2000 required for commissioning
MS1224UF
Silver Series Regulating LightSpot
24V AC/DC Operation
Electrical Connections
Red
Black
24V AC/DC
Supplied pre-wired to
the following plugs:
Metway GSK86502
Volt-free
output
Ballast
control
Green -
White
Blue
Black
White
Green
Red
Yellow
Blue
Wieland 25.380.3353.0
Ex-Or
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 272767
Email: technicalsales.ex-or@honeywell.com
www.ex-or.com
At the end of their useful life
the packaging and product
should be disposed of via a
suitable recycling centre.
Do not dispose of with normal
household waste.
Do not burn.
6.0m