background image

Update le 01/07/2015

ITEM

SW1, SW2, SW3, SW4

Tone

Frequency

Tone Description

Tone Application

Waveform dB@1meter

Bit 123456

DC (mA) AC (mA)

00

0

0

0

0

0

000000

60

10

01

300Hz

Continuious

105

100000

925

105

02

340Hz

Continuious

105

010000

925

105

03

440Hz

Continuious

105

110000

950

105

04

554Hz

Continuious

106

001000

925

99

05

660Hz

Continuious

All‐clear, Sweden

104

101000

904

90

06

800Hz

Continuious

105

011000

795

78

07

1000Hz

Continuious

PFEER Toxic Gas

109

111000

840

80

08

1200Hz

Continuious

106

000100

930

83

09

2000Hz

Continuious

105

100100

990

69

10

2400Hz

Continuious

103

010100

945

60

11

2850Hz

Continuious

102

110100

880

48

12

450Hz@0.625 sec

Intermittent

Australian, AS2220

100

001100

1050

117

13

544Hz@0.875sec

Intermittent

104

101100

1000

106

14

660Hz@150ms on, 150ms off

Intermittent

Swedish Fire Alarm

100

011100

960

96

15

660Hz@1.8 sec on, 1.8sec off

Intermittent

Swedish Fire Alarm

103

111100

985

100

16

745Hz@500ms on, 500ms off

Intermittent

102

000010

840

84

17

800Hz@250ms on, 250ms off

Intermittent

102

100010

820

76

18

800Hz@250ms on,1s off

Intermittent

100

010010

850

84

19

1000Hz@250ms on, 250ms off

Intermittent

105

110010

890

80

20

1000Hz@500ms on,500ms off

Intermittent

Back‐up Alarm (LF)

105

001010

870

82

21

1000Hz@250ms on,1s off

Intermittent

105

101010

900

84

22

1000Hz@1s on,1s off

Intermittent

PFEER Gen, Alarm

105

011010

890

83

23

2400Hz@250ms on, 250ms off

Intermittent

101

111010

1020

62

24

2400Hz@500 ms on,500ms off

Intermittent

100

000110

1010

50

25

2850Hz@1s on, 1s off

Intermittent

Back‐up Alarm (HF)

101

100110

930

50

26

2850Hz@150ms on, 100ms off

Intermittent

Pelican crossing

101

010110

900

82

27

970Hz@500ms on,500ms off, 1.5s off

3 Pulses

ISO 8201 Low Tone

105

110110

870

51

28

2850Hz@500ms on, 500ms off, 1.5s off

3 Pulses

ISO 8201 Low Tone

101

001110

950

90

29

700Hz@2s on, 2s off

Intermittent

Air‐raid, Sweden

105

101110

890

86

30

700Hz@125ms on, 125ms off

Intermittent

Local Warning, Sweden

105

011110

875

87

31

720Hz@0.7s on, 0.3s off

Intermittent

Industrial alarm, Germany

105

111110

875

102

32

544Hz/440Hz@500ms

Alternating

Swedish Fire Alarm

101

000001

970

104

33

544Hz/440Hz@100ms/400ms

Alternating

AFNOR, NFS 32‐001

101

100001

960

102

34

544Hz/400Hz@1s

Alternating

Turn‐out, Sweden

100

010001

970

80

35

800Hz/1000Hz@125ms

Alternating

Increased Urgency

104

110001

830

55

36

2400Hz/2900Hz@125ms

Alternating

Security Deterrent

100

001001

950

78

37

800Hz/1000Hz@250ms

Alternating

Fire Alarms

104

101001

830

78

38

800Hz/1000Hz@580ms

Alternating

104

011001

840

75

39

1000Hz/2000Hz@500ms

Alternating

104

111001

1020

55

40

2400Hz/2900Hz@250ms

Alternating

Security Alarms

100

000101

950

92

41

500Hz‐‐1000Hz@6Hz

Fast Whoop

103

100101

900

102

42

500Hz‐‐1000Hz@0.3Hz

Sweeping

102

010101

1000

80

43

660Hz‐‐1200Hz@1Hz

Sweeping

101

110101

910

78

44

800Hz‐‐1000Hz@1Hz

Med Sweeping (LF)

101

001101

830

78

45

800Hz‐‐1000Hz@7Hz

Fast Sweeping (LF)

102

101101

800

55

46

2400Hz‐‐2900Hz@1Hz

Sweeping

100

011101

930

55

47

2400Hz‐‐2900Hz@7Hz

Fast Sweeping

100

111101

910

75

48

800Hz‐‐1000Hz@50Hz

Low freq buzz

Buzz

100

000011

810

55

49

2400Hz‐‐2900Hz@50Hz

High freq buzz

Buzz

100

100011

900

103

50

500Hz‐‐1200Hz@2.5s ↑ 0.5s

Slow Whoop

102

010011

1010

102

51

500Hz‐‐1200Hz@5s ↑ 0,25s

Slow Whoop

Evacuation, Netherlands

102

110011

1000

104

52

1200Hz‐‐500Hz@1Hz

Reverse Sweeping

Evacuation, Germany

102

001011

960

84

53

1400Hz‐‐1600Hz@1s ↑ 0,5s ↓

Sweeping

NFC 48‐265

100

101011

1040

66

54

Simulated bell

Fast Shake

Bell

98

011011

860

102

55

800Hz/660Hz

Tow tone chime

Int'l evacuation alarm

102

111011

980

102

56

800Hz/1000Hz

ISO 8201 Evacuation

Int'l evacuation alarm

102

000111

880

81

57

250Hz‐‐1200Hz@3s ↑, 6s, 3s ↓

Motor Siren‐slow rise

104

100111

1000

107

58

250Hz‐‐800Hz@3s ↑, 6s, 3s ↓

Motor Siren‐slow rise

105

010111

1020

108

59

250Hz‐‐1400Hz@3s ↑, 6s, 3s ↓

Motor Siren‐slow rise

100

110111

950

106

DESCRIPTION

COMSUPTION

Summary of Contents for SD125

Page 1: ...P66 Ex tb IIIC Txxx EX TECH SIGNALLING SAS SD125 150 EXPLOSION PROOF SOUNDER HORN TECHNICAL MANUAL Marking details Please note that every care has been taken to ensure the accuracy of our technical ma...

Page 2: ...Warning DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT Finish product serial no Include date of construction Note exact information is given on the actual label ref also example on page 1 3...

Page 3: ...ioned such that dust debris or water cannot enter into the horn opening but operate in reverse manner as above 6 0 WIRING General Requirement EX TECH SIGNALLING SAS recommends that all cables and core...

Page 4: ...m EX TECH SIGNALLING SAS in advance before EX TECH SIGNALLING SAS begin the production of the sounder 11 0 CABLE GLAND 8 0 VOLUME CONTROL The sounder has a volume control to adjust the output volume o...

Page 5: ...exterior of the product can be cleaned with a damp cloth If spare parts are required these can be supplied by EX TECH SIGNALLING SAS Company SAFETY WARNING In the case of Anti Static and UV Resistant...

Page 6: ...EX TECH SIG SAS 12 SD125 150 TM EN REV04 Attached Table 2 Tone Selection Table 6...

Page 7: ...S 12 SD125 150 TM EN REV04 EX TECH SIGNALLING SAS ZA Les Montagnes 355 rue de la G noise 16430 CHAMPNIERS France Tel 33 5 45 61 81 68 Fax 33 5 45 23 29 46 Website www ex tech no E mail sales signallin...

Page 8: ...Hz 2s on 2s off Intermittent Air raid Sweden 105 101110 890 86 30 700Hz 125ms on 125ms off Intermittent Local Warning Sweden 105 011110 875 87 31 720Hz 0 7s on 0 3s off Intermittent Industrial alarm G...

Page 9: ...is on 4 The unit will alarm as stage 1 when switch 1 is on The unit will alarm as stage 2 when switch 2 is on The unit will alarm as stage 3 when switches 1 2 are on Telephone Initiated PCB Function...

Page 10: ...The unit will alarm as stage 2 when switch 2 is on The unit will alarm as stage 3 when switches 1 2 are on Telephone Initiated PCB Function 1 Connect the telephone line to the Tel terminals 2 The unit...

Reviews: