7
A configured CoolX has the following galvanic isolation barriers.
Isolation Barrier
Type
Withstand Voltage
Input to Output
Reinforced (2 x MOPP)
4000VAC
Input to Case (GND)
Basic (1 x MOPP)
1850VAC
Output to Case (GND)
Basic (1 x MOPP)
1850VAC
Output to Output
Basic (1 x MOPP)
1850VAC
Output (V1) to Output (V2) - Dual
Functional
500VAC
Summary of Contents for CoolX1800
Page 29: ...29 ...
Page 71: ...71 CoolX1800 2 x Bulk Modules ...