4.4 ELECTRICAL CONNECTIONS
Before connecting the hoist to the power supply, check that voltage and power of the electric supply
corresponds to those reported on the chain hoist plate. Check also that the earthing system is efficient.
Do not insert the plug of the hoist directly into a power socket. Only use a dedicated chain hoist controller.
Installers must equip the branch circuit with a grounding system, protection against current overloads and
short circuits that comply with the requirements of the laws on safety and health protection on work place of
the Country where the hoist is installed.
In order to avoid risk of electrocution and malfunction, check that all cables powering the hoist are protected
against possible external damages.
EXE Rise chain hoists are available in both direct and low voltage control. They must be connected to a
power and control system that is suitably designed to operate the chain hoists and handle the power
consumption of the motor.
EXE Rise hoists are factory set to be run with a voltage of 400 V AC. The DC hoist is fitted with a CEE 16A
6h 400VAC
– 3PH +G black plug. plug as standard. The LVC hoist comes with a CEE 16A 4h 110VAC -
3PH +G black socket.
Electrotechnical adjustments may only be performed by authorised specialists.