Digital outputs to actuate a Relay
When the digital output is used to actuate a relay coil a protection diode must be added to the connection
to avoid damage to the output of the equipment. This must be connected in reverse, that is the anode to
the output terminal of the equipment and the cathode to the positive terminal feeding the relay. The relay
must be fed using an external power supply, sharing the GND terminal with the power supply of the
equipment, or if necessary the same power supply feeding the GRD can be used.
The following graph shows how to connect a relay to a digital output of the equipment.
Analog Inputs
Analog inputs refer to the GND Terminal of the equipment, consequently, the power supply used to feed
the sensor must share the GND terminal with the equipment.
Voltage inputs (0-10V / 0-1V)
Parameter
Value
Units
Full scale
10 / 1
Vdc
Precision
1 / 0.1
mV
Input impedance
11.4
KΩ
The following two examples show how to connect and analog voltage input for a single power
supply or for independent power supplies.
GRD-MQ User Manual
Features of power supply and inputs/outputs
30 / 84
Summary of Contents for GRD-MQ Series
Page 26: ...Analog inputs GRD MQ User Manual Physical Inputs Outputs 25 84 ...
Page 33: ...2020 09 28 GRD MQ User Manual Features of power supply and inputs outputs 32 84 ...
Page 74: ...2020 11 20 GRD MQ User Manual Scripts Publish Subscribe 73 84 ...
Page 76: ...Wiring Terminal Blocks 2020 10 05 GRD MQ User Manual GRD1620 MQ 3G 75 84 ...
Page 79: ...2020 10 05 GRD MQ User Manual GRD3621 MQ 3G 78 84 ...
Page 83: ...Wiring Terminal Blocks 2020 10 05 GRD MQ User Manual GRD3534 MQ 3G 82 84 ...