By alarm
This criterion defines an operational band through a maximum and minimum. When the analog input
exceeds the maximum value a Historical is generated by maximum, when the analog input is lower than
the minimum a Historical by minimum is generated and when the analog input passes from a maximum
value or from a minimum value to a normal value between both a Historical by normal value is generated.
In this manner we can follow the evolution of the input when it fluctuates between the specified limits. In
addition to the maximums and minimums a value of hysteresis must be defined to avoid continuous
generation of Historicals when the analog signal oscillates above a threshold value. In the following figure
we can see how the hysteresis mechanism works for the maximum.
The same happens for minimum values but in an exactly opposite manner.
GRD-MQ User Manual
Reports and Historical records
48 / 84
Summary of Contents for GRD-MQ Series
Page 26: ...Analog inputs GRD MQ User Manual Physical Inputs Outputs 25 84 ...
Page 33: ...2020 09 28 GRD MQ User Manual Features of power supply and inputs outputs 32 84 ...
Page 74: ...2020 11 20 GRD MQ User Manual Scripts Publish Subscribe 73 84 ...
Page 76: ...Wiring Terminal Blocks 2020 10 05 GRD MQ User Manual GRD1620 MQ 3G 75 84 ...
Page 79: ...2020 10 05 GRD MQ User Manual GRD3621 MQ 3G 78 84 ...
Page 83: ...Wiring Terminal Blocks 2020 10 05 GRD MQ User Manual GRD3534 MQ 3G 82 84 ...