background image

EXHAUSTO A/S

Odensevej 76

DK-5550 Langeskov

Tel. +45 65 66 12 34

Fax +45 65 66 11 10

exhausto@exhausto.dk

www.exhausto.dk

Art.-no. 

 GAUMBGATEWAY001

P0101_BO_0001

• Network Module

MB-

gateway

Technical manual

3005392-2015-10-28

Summary of Contents for GAUMBGATEWAY001

Page 1: ...A S Odensevej 76 DK 5550 Langeskov Tel 45 65 66 12 34 Fax 45 65 66 11 10 exhausto exhausto dk www exhausto dk Art no GAUMBGATEWAY001 P0101_BO_0001 Network Module MB gateway Technical manual 3005392 20...

Page 2: ...e setting window 9 4 3 Fan speed setting window 10 4 4 Fault List window 11 4 5 Menu window 12 4 6 Settings window Set the BOOST function time 13 4 7 Settings window Set the desired CO2 level 14 4 8 S...

Page 3: ...B MicroSD memory card 2 Sticker with a MAC address and fields for writing down connection settings 3 UTP cable 0 5 m 4 RS485 communication cable with RJ11 plugs 2 m 5 Adapter 6 Installation Manual EN...

Page 4: ...0 51 into the browser Google Chro me is recommended address bar 5 Each page is password protected When you open the configuration page you will be asked to en ter user name and password Default user...

Page 5: ...to the normal state 4 When the update is finished the file FIRMWARE BIN is automatically deleted Indications of the RJ45 connector LEDs Both LED indicators flashes slowly and synchronously MB GATEWAY...

Page 6: ...ick to switch to the Italian language Click to open the control window of automatics The automatics is recognised automatically If parameters of the RS485 communication line are wrong or the device is...

Page 7: ...ication line is set The date and time of MB GATEWAY module is set The user name of the MB GATEWAY module is set The password of the MB GATEWAY module is set The password of the MB GATEWAY module is re...

Page 8: ...active Displays the date and time Displays the outdoor air temperature Displays the extract room air temperature Displays the supply air temperature Displays the extract air humidity I1 I4 I2 I5 I3 I...

Page 9: ...rature setting Click to turn on off the ventilation Click to turn on off the BOOST function now it is active Click to turn on off the Stand by mode Click to open the Alarms list window It is displayed...

Page 10: ...Click to return to the main window Click to activate the Stand by mode Click to turn on the fan speed 1 Click to turn on the fan speed 2 Click to turn on the fan speed 3 Click to turn on off the BOOS...

Page 11: ...B2 EN B1 B2 I1 Meaning Plate heat exchanger frost protection function Fire alarm Dirty filter alarm Fans overheat alarm Low voltage DJT 100 temperature sensor alarm Exhaust air temperature sensor alar...

Page 12: ...ck to open the settings window Click to open the status monitoring window Click to open the weekly schedule setting window Click to switch to the green theme Click to switch to the blue theme Click to...

Page 13: ...The selection is active when the CO2 sensor is used currently inactive Click to open the night time cooling function settings window Click to open the date and time settings window Click to open the...

Page 14: ...el 4 Number Function Click to return to the settings window Click to increase decrease the CO2 level setting Number Function Displays the desired CO2 level setting PPM I1 B1 B2 B3 EN B2 B3 I1 B1 The s...

Page 15: ...oom air temperature setting Click to increase decrease the minimum outdoor air temperature setting Click to increase decrease the air change interval setting in hours B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 4...

Page 16: ...ck to increase decrease the month setting Click to increase decrease the year setting Click to increase decrease the hour setting Click to increase decrease the minute setting B1 B2 B3 B8 B4 B9 B5 B6...

Page 17: ...unction Click to return to the settings window Click to reset the filter timer B1 B2 Number Function Displays the remaining filter time in hours Displays the set filter timer limit in hours Displays w...

Page 18: ...circuit turned on off Set Point system temperature Extract air humidity Active system mode The state of the heater power circuit turned on off The state of the by pass valve The state of the stand by...

Page 19: ...ick to delete the event Click to copy the event details B1 B2 B3 B13 B4 B5 B6 B12 Number Function Displays the event number 8 total events per day Displays the selected weekday Displays the hour of ev...

Page 20: ...k to delete weekday events Click to paste day s events from clipboard B1 B4 B2 B3 Click to paste copied details of another event Click to decrease increase hour value Click to decrease increase minute...

Page 21: ...imal representation of variable address o e value for writing request or amount for reading request when reading some consecu tive addresses Full Modbus request with CRC http address F request g http...

Page 22: ...o 03 Modbus command Read Holding Registers o 2387 starting with address 9095 0x2387 o 0006 6 variables o delimiter o 01 write to a device that has an address of 01 o 10 Modbus command 16 0x10 Preset...

Reviews: