2.3.1 Control fuses integrated in VEX100 with electric heating coil
VEX size
Output HCE
[kW]
Fuse for control
system (1x230V)
2 pole
Fuse for MC1
(1x230V) 2 pole
Fuse for MC2
(1x230V) 2 pole
Common fuse for
MC1 and MC2
(3x400V) 3 pole
VEX140
7,2
C-10A
C-10A
C-10A
14,4
C-10A
C-10A
C-10A
VEX150
12
C-10A
C-10A
C-10A
18
C-10A
C-10A
C-10A
VEX160
14,4
C-10A
C-16A
C-16A
21,6
C-10A
C-16A
C-16A
28,8
C-10A
C-16A
C-16A
VEX170
31,2
C-10A
C-20A
46,8
C-10A
C-20A
Voltage: 3 x 400V+N+PE
VEX size
Output HCE
[kW]
Fuse (1) for HCE
(3x400V) 3 pole
Fuse (2) for HCE
(3x400V) 3 pole
Fuse (3) for HCE
(3x400V) 3 pole
Number of
fuses
VEX140
7,2
C-16A
4
14,4
C-25A
4
VEX150
12
C-25A
4
18
C-25A
C-16A
5
VEX160
14,4
C-25A
4
21,6
C-25A
C-16A
5
28,8
C-25A
C-25A
5
VEX170
31,2
C-25A
C-25A
4
46,8
C-25A
C-25A
C-25A
5
Voltage: 3 x 400V+N+PE
3004524-2014-08-27
Installation of the VEX
15/24