3.4.3 MVM valve
Screening
Screen the valve motor from direct sunlight. Due to heat emissions, the valve mo-
tor must not be encapsulated (max. ambient temperature: 50°C).
Insulating the valve
To ensure normal operation at ambient temperatures below 0°C, it is very impor-
tant that the valve section is insulated according to current standards.
Regulation proper-
ties
The motor valve's regulation properties are best when the differential pressure is
between 5-20 kPa. See section "Technical specifications" to calculate K
vs
.
Water supply
The water supply
must
be constant. This applies to both cold and hot water sup-
ply.
3005993-2021-03-09
Mechanical installation
26/44