3005831-2019-04-01.fm
Mechanical assembly
11/64
3.1.2 Setting up the base
Place the base on a suitable installation site that has a foundation and which has been
prepared. If the base is separated, assemble the cross members using mounting tabs.
3.1.3 Positioning and assembly of sections
Numbers written in parenthesis is the following section, refer to loose parts that are
named in the section
“Extent of delivery”
.
Assemble the sections on the base in numerical order, starting with no. 1, from left to
right. If the system is a 2-string system, align the top sections in after the bottom
sections.
The section numbers are stated on the information plates on the sections.
1. Fit a levelling screw under each tab joint.
2. Fit and adjust the remaining levelling screws in the holes in the member so
that the foundation is levelled.
The distance between the levelling screws
may not exceed 1300 mm, this
is ensured by using the pre-bored holes in the side members.
Important:
The base must be completely level, otherwise the sections
will twist when they are subsequently fitted
and the doors will not seal properly when closed.
1. Remove the transport feet before the sections are placed on the base.
2. Fit the plastic covers where the feet were and secure the section to the
base using the fittings (4) and bolts.
3. Secure the air handling unit on the side of the base using the fittings that
have hooks in the ends (3). Use 6.3 x 1.3 mm sheet metal screws.