F2.01
Start frequency
0.20~60.00Hz
0.50Hz
F2.02
Start frequency hold time
0.0~10.0s
0.0s
The start frequency refers to the initial frequency when the drive starts, and start
frequency hold time refers to the time when the drive keeps running at the start frequency
during the start process, as shown in t1 in Figure 6-8.
.
Figure 6-8 Schematic Diagram of Start Frequency and Start Time
Note: The start frequency is not restricted by the lower limit frequency.
F2.03
Start DC braking current
0.0 ~ 100.0% motor rated
current
80.0%
F2.04
Start DC braking time
0.0~30.0s
0.0s
F2.03 and F2.04 are valid only when the first braking then starting (F2.00=1) is
selected as start-up mode, as shown in Figure 6-9.