EXPERT Standard Series User Manual
122
6.6 Group F5 frequency given parameters
F5.00
Frequency given curves
selection
0000~1111
0000
F5.01
Given channel gain
0.000~9.999
1.001
F5.02
Given filter time
0.001~50.000s
0.010s
F5.03
Maximum
input
pulse
frequency
0.1~50.0kHz
10.0kHz
F5.04
Minimum given of curve 1
0.0%~F5.06
0.1%
F5.05
Frequency corresponding
to minimum given of curve
1
0.0~F1.06
0.00Hz
F5.06
Maximum given of curve 1
F5.04~100.0%
100.0%
F5.07
Frequency corresponding
to maximum given of curve
1
0.0~F1.06
50.00Hz
F5.08
Minimum given of curve 2
0.0%~F5.10
0.1%
F5.09
Frequency corresponding
to minimum given of curve
2
0.0~F1.06
0.00Hz
F5.10
Maximum given of curve 2
F5.08~100.0%
100.0%
F5.11
Frequency corresponding
to maximum given of curve
2
0.0~F1.06
50.00Hz
Select AI1 or AI2 or pulse frequency or AI3 input of expansion card as the open-loop
frequency given channel, the relationship between the given and set frequency is shown in
figure 6-17:
Figure 6-17 Relationship between Given Channel Input and Set Frequency
After filtering and gain processing, the relationship between the given frequency signal
and the set frequency is determined by curve 1 or curve 2. Curve 1 is defined by F5.04~
F5.07, and curve 2 is defined by F5.08 ~ F5.11. Both can realize positive action and
negative action characteristics independently, as shown in Figure 6-18.