EXPERT Standard Series User Manual
151
The extended function 2 of the upper computer is to directly control the output of AO1
and AO2 through the serial port. 1000 corresponds to the maximum output 10V (or 20mA),
please refer to this communication protocol.
For example:
AO1 outputs 4~20mA, corresponding to indication bus voltage 0~800V.
The settings are as follows:
1
When F6.24=7, it outputs bus voltage;
2
When F6.26=01, the AO1 output type is 4~20mA;
3
When F6.27=100%, the output gain is 100%;
4
When F6.29 LED unit digit=1, it outputs current type.
F6.26
Analog output range
selection
00~11
00
Figure 6-34 Analog Output Offset Setting
This function code is used to select the analog output range of AO1 and AO2.
F6.27
AO1 output gain
0.0~200.0%
100.0%
F6.28
AO2 output gain
0.0~200.0%
100.0%