Table 6-15 Starting Conditions for Restart from Power Failure
FC.22 settings
Before
power
failure
Status
Operate
Panel
Serial port
Terminal
three-wire type
1 and 2
Terminal two-wire
type 1 and 2
Run command at power on moment: None
Yes
0
Stop
0
0
0
0
0
Run
0
0
0
0
0
1
Stop
0
0
0
0
1
Run
0
0
0
0
1
Note: Table 6-15 shows the actions of the drive under various combination conditions
and after power-on, 0: Enter standby state; 1: Start running automatically. When the
operation panel, serial port and terminal three-wire type 1 and 2 control the start and stop, it
is a pulse command mode, and there’s no run command at power-on moment. If there’s a
stop command, stop first.
When restart from power failure is valid, if power on not after complete power failure
during running (i.e. The drive LED displays “P.OFF”), it will start automatically according to
the speed tracking mode during restart; if power on after complete power failure (i.e. The
LED on the operation panel lights off), it will start according to the setting of start mode
F2.00 during restart.
FC.24
Run
command
channel
binding
frequency
given
channel
000~888
000
This function defines the binding combinations between three run command
channels and eight frequency given channels, which is convenient to realize
synchronous switching.